Raypak Hi Delta 992B-1262B User Manual

Page 42

Advertising
background image

42

Ignition Module

When additional heat is needed, the combustion air
blower starts to purge air from the combustion cham-
ber for about 15 seconds. On proof-of-air flow, the air-

proving switch closes and the igniter is energized. To
ensure safe operation, the gas valve cannot open until
the igniter is verified. The main burner is automatically
lit when the device is powered and pre-purged. The
heater performs its own safety check and opens the
main valve only after the igniter is proven to be capa-
ble of ignition.

The standard ignition module will attempt to light three
times before locking out. To reset it, turn off power to
the heater, wait 30 seconds and re-apply power.

Code

Condition

On

System OK;

No faults present

Off

Possible control fault;

Check power

1 Flash

Low air pressure, brief

flashing normal on start-up

2 Flashes

Flame in combustion

chamber; No call for heat

3 Flashes

Ignition lockout

4 Flashes

Low igniter current

5 Flashes

Low 24 VAC, check control

supply voltage

6 Flashes

Internal fault;

Replace module

Fig. 32: Ignition Module

Table N: Ignition Module Diagnostic LED Codes

The optional single-try ignition module will lock out
after failing to light one time. To reset it, press and
release the small, recessed black push button located
inside of the cut-out on the lower right-hand corner of
the ignition module case. Turning off the power to the
heater WILL NOT reset the ignition module.

High Limit (Manual Reset)

The heater is equipped with a manual reset high limit
temperature device. Push the reset button and adjust
the setting to 40 - 50°F above desired operating tem-
perature.

Flow Switch

This dual-purpose control, mounted and wired in
series with the main gas valve, shuts off heater in case
of pump failure or low water flow.

Operating Control

The heater may be equipped with different types of
operating controls. Consult the individual control data

Fig. 33: High Limit (Manual Reset)

Fig. 34: Flow Switch