Fig. 34: Fan-Proving Switch

Fig. 35: Blocked Vent Switch

UDB Diagnostic Board

This heater is equipped with a diagnostic board which

will indicate faults as they occur. Refer to the following

section for instructions on accessing, reviewing and

clearing these faults.

UDB Fault History

To view the fault codes in the UDB history file:

1. Press the UP or DOWN buttons on the membrane

switch for 2 seconds to access the fault history.

2. Press either button to scroll through the recorded

faults in history.

3. The most recent fault recorded will be the first fault

displayed (the last 16 faults are stored in the his-

tory, on a rolling basis). There is no time or date

stamp associated with these faults.

4. When the history of faults has been exhausted,

pushing the UP or DOWN buttons again will roll

the fault history over and it will start again.

5. To exit the fault history, wait for 10 seconds and

the board will automatically exit the history mode.

To clear the fault history, press and hold both the UP

and DOWN buttons for 5 seconds while the power is

on.

Diagnostic information is provided any time a fault is

recorded. This information is intended to assist in

locating the problem with the heater, but is not exhaus-

tive.

If multiple fault conditions occur at the same time, only

the fault that caused the heater to shut down will be

recorded in the history.

Fig. 37: UDB Diagnostic Board

Pump Time Delay

The Economaster is a fully enclosed solid state TDR

with a white jumper that selects one of two time

delays. See Fig. 36. If the jumper is on pins 6 and 7

(default) the delay time is 5 minutes. If the jumper is

not on pins 6 and 7, the time delay is 10 minutes.

In a conventional system, when the Aquastat is satis-

fied, the main gas valve closes, but the pump

continues operating. With the time delay relay the boil-

er pump is programmed to continue running for an

optimum period of time in order to absorb the residual

heat from the combustion chamber and use it in the

system. The pump then shuts off until the next call for

heat is received from the Aquastat.

Fig. 36: Economaster Time Delay Relay (TDR)

NOTE: Once the history has been cleared, it cannot

be recovered.