Installation, Mantel leg clearances, Mantels – Regency P42-NG4 User Manual

Page 8: Clearances

Advertising
background image

Regency

®

P42-4 Zero Clearance Direct Vent Gas Fireplace

8

MANTEL LEG CLEARANCES

Combustible mantel leg clearances as per diagram below:

MANTELS

Because of the extreme heat this fi replace emits, the mantel clearances are critical.
Combustible mantel clearances from louver are shown in the diagram below.

Note: A non-combustible mantel may be installed at a lower height if the framing is made

of metal studs covered with a non-combustible board.

INSTALLATION

This drawing is to scale at 1:6 (one inch = 6 inches)

Mantel can be installed anywhere in shaded area using the above scale for units with the Flush
Front and with the optional Bay Front.

Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the

paint may discolour.

Maximum
1-1/2" projection at 2"
minimum clearance.

CLEARANCES

The clearances listed below are Minimum
distances unless otherwise stated:

A major cause of chimney related fi res is
failure to maintain required clearances (air
space) to combustible materials. It is of the
greatest importance that this fi replace and
vent system be installed only in accordance
with these instructions.

Clearance to Combustibles from:
Back
0"

(0mm)

Side 0"

(0mm)

Floor 0"

(0mm)

Minimum Clearance from Louver to:
Mantel
min.

7"

(177mm)

Ceiling 36" (914mm)

from

top

of

louvers

Side Wall 6"

(152mm)

Vent 1-1/2"

(38mm)

Flex

1-1/4" (32mm)

Rigid

Pipe

Alcove Clearances:
Max. Depth
36"

(914mm)

Min. Width 52"

(1321mm)

Min. Height 90"

(2286mm)

WARNING

Fire hazard is an extreme risk

if these clearances are

not adhered to.

The HeatWave Duct Kit
and the Heat Release
K i t h a v e d i f f e r e n t
clearance and framing
requirements, check
the HeatWave and Heat
Release manual for
details.

Heat Release Kit