RETURN TEMPERATURE

The return sensor is used to compensate for seasonal changes in loop heat loss. The strategy may
raise the supply/branch temperature in cold weather to ensure that the last rooms on the loop
have hot enough water even during low demand periods.

R0 SELECT - Return Sensor Installed

Select YES if this sensor is connected, otherwise select

NO. Default is YES.

R1 SELECT - Minimum Return Temperature

If the return temperature drops below this

value then the return sensor strategy will be activated. Above this value, the strategy will have no
effect on desired temperature. Default Temp 108°F.

R2 SELECT - Return Sensor Response

This is a multiplier which increases the desired tem-

perature as the return temperature drops. Example: desired = 130, return = 100, R1 (above) = 102,
R2 = 5. The desired temperature will be increased to 140 = 130 + (102-100) X 5. Default Value
is 1.