Maximum delivery, Recovery capacities, Dimensional information – Rheem Induced Draft User Manual

Page 2: Clearances to combustibles, Limited warranty

Advertising
background image

Recommended Specifications
(for trade reference only)

Water heater(s) shall be

Induced Draft

model

________________, manufactured by RHEEM-RUUD,
having gas input of __________ Btu/hr. and a recovery rate
of _____________ GPH at a 100°F temperature rise when
tested and certified at ____________ thermal efficiency.
Water heater(s) shall have a storage capacity of _________
gallons. Water heater(s) shall have the CSA seal of certifica-
tion and supplied with a factory installed AGA/ASME rated
temperature and pressure relief valve. Tank(s) shall be
furnished with a tube bundle having a double coating of high
temperature porcelain enamel and furnished with magnesium
anode rods rigidly supported. Water heater(s) shall meet or
exceed the thermal efficiency and standby loss requirements
of ASHRAE. Tanks shall have a working pressure rating of
150 psi, and shall be completely factory assembled, including
a pressure regulator properly adjusted for operation on
___________ gas with stainless steel burners. Controls will
be arranged for safety shutoff in event of pilot failure. Water
heater(s) with inputs less than 360,000 Btu/hr. shall have top, front and rear side inlet/outlet water connections.
Water heater(s) shall be covered by a three year limited warranty against tank leaks.

• Add for ASME construction –

Water heater(s) shall be constructed in accordance with the requirements of the
ASME Boiler and Pressure Vessel Code, Section IV Part HLW.

Limited Warranty

This product features a three year limited warranty against tank leaks. Please refer to
Commercial Warranty Information brochure for complete warranty information.

MODEL

TANK CAPACITY

INPUT BTU/HR.

TEMP.

5

10

15

20

30

45

60

120

180 MIN. TO REC.

NUMBER GALS.

LITERS

NAT.

& L.P.

RISE

UNITS

Min.

Min. Min.

Min.

Min. Min. Min.

Min. Min.

CONTENTS

GD100-250(A)

100

379

250,000

100°F

GAL.

90

110

131

151

191

252

312

555

797

25

37.7°C

LTR.

341

418

494

571

724

953

1183

2100

3018

GD100-270(A)

100

379

270,000

100°F

GAL.

92

114

135

157

201

266

332

594

855

23

37.7°C

LTR.

348

430

513

595

761

1008

1256

2247

3238

GD100-310(A)

100

379

310,000

100°F

GAL.

95

120

145

170

220

295

371

671

972

20

37.7°C

LTR.

360

455

549

644

834

1118

1403

2541

3679

GD100-360(A)

100

246

360,000

100°F

GAL.

99

128

157

186

245

332

419

768

1117

17

37.7°C

LTR.

375

485

596

706

927

1258

1588

2911

4234

MAXIMUM DELIVERY

In U.S. Gallons and Liters. (Includes useable storage and recovery for indicated times.)

Induced Draft Gas continued.

MODEL

INPUT BTU/HR.

THERMAL

40°F

50°F

60°F

70°F

80°F

90°F 100°F 110°F 120°F 130°F 140°F

NUMBER

NATURAL & L.P.

EFFICIENCY

UNITS

22°C

28°C

33°C

39°C

45°C

50°C

56°C

61°C

67°C

72°C

78°C

GD100-250(A)

250,000

80%

GPH

606

485

404

346

303

269

242

220

202

186

173

LPH

2294

1835

1529

1311

1147

1020

918

834

765

706

655

GD100-270(A)

270,000

80%

GPH

655

524

436

374

327

291

262

238

218

201

187

LPH

2478

1982

1652

1416

1239

1101

991

901

826

762

708

GD100-310(A)

310,000

80%

GPH

752

601

501

429

376

334

301

273

251

231

215

LPH

2845

2276

1896

1626

1422

1264

1138

1034

948

875

813

GD100-360(A)

360,000

80%

GPH

873

698

582

499

436

388

349

317

291

269

249

LPH

3304

2643

2202

1888

1652

1468

1321

1201

1101

1016

944

Recovery ratings are based on thermal efficiencies obtained in a CSA certified laboratory. Recovery rate shown on the rating plate (75%) thermal efficiency in accordance
with ANSI Z21.10.3 labeling requirements. (A) indicates available ASME model.

RECOVERY CAPACITIES

Recovery in U.S. Gallons/Hr. (GPH) and Liters/Hr. (LPH) at Various Temperature Rises.

WATER CONNECTIONS

APPROXIMATE

MODEL

TOP

FRONT

REAR

SHIPPING WEIGHT

NUMBER

UNITS

A

B

C

D E F G H

IN/OUT

SIDE

SIDE

STD.

ASME

GD100-250(A)

inches

73-1/2

66-3/4

30-1/4

23-1/4

6

57-1/2

3/4

23

1-1/2

2

2

795 lbs.

835 lbs.

mm

1867

1696

768

591

152

1460

19

584

38

51

51

360 kgs.

378 kgs.

GD100-270(A)

inches

73-1/2

66-3/4

30-1/4

23-1/4

6

57-1/2

3/4

23

1-1/2

2

2

795 lbs.

835 lbs.

mm

1867

1696

768

591

152

1460

19

584

38

51

51

360 kgs.

378 kgs.

GD100-310(A)

inches

73-1/2

66-3/4

30-1/4

23-1/4

6

57-1/2

3/4

23

1-1/2

2

2

795 lbs.

835 lbs.

mm

1867

1696

768

591

152

1460

19

584

38

51

51

360 kgs.

378 kgs.

GD100-360(A)

inches

73-1/2

66-3/4

30-1/4

23-1/4

6

57-1/2

3/4

23

1-1/2

2

2

795 lbs.

835 lbs.

mm

1867

1696

768

591

152

1460

19

584

38

51

51

360 kgs.

378 kgs.

All models require a 120V /3 amp power source. (A) suffix indicates ASME tank construction available.

DIMENSIONAL INFORMATION

All Dimensions Shown in English and Metric.

C

H
E

A

B

F

D

OUTLET

TOP

INLET

TOP

OUTLET

FRONT SIDE

OUTLET

REAR SIDE

SYSTEM

SENTINEL

T&P

INLET

FRONT SIDE

INLET

REAR SIDE

G

7"

(178mm)

1

1

12

25

25

305

1

1

12

25

25

305

1

1

12

25

25

305

1

1

12

25

25

305

GD100-250(A)

inches

mm

GD100-270(A)

inches

mm

GD100-310(A)

inches

mm

GD100-360(A)

inches

mm

CLEARANCES TO COMBUSTIBLES

MODEL
NUMBER

UNITS

SIDE

REAR

TOP

Allow a minimum of 18" (457mm) front clearance for servicing.

C O M M E R C I A L

W A T E R H E A T E R S

Rheem Water Heating • 101 Bell Road, Montgomery, Alabama 36117-4305 • www.rheem.com
Rheem Canada Ltd./Ltée,128 Barton Street West, Hamilton, Ontario L8N 3P3

P R I N T E D I N U . S . A .

1 1 / 0 6 W P

F O R M N O . R R 1 0 2 C - 9

In keeping with its policy of continuous progress and product improvement, Rheem-Ruud reserves the right to make changes without notice.

Advertising