SERIAL PORTS

SECTION 4

Page 4-2 RPC -320

Figure 4-2 Network diagram

400 LINEB 5,0,(LINEB(5,0) .AND. 251)
500 LINEB 5,0,(LINEB(5,0) .OR. 4)

Jumper W 4 determines if COM 1 receive is RS-232 or
RS-422/485.

W4[1-2]

RS-485

W4[2-3]

RS-232 (de fault)

C O M 1 d ef a ul t i s R S -2 3 2. U s e th e C O NF I G BA U D
statement to set the software to RS-422 or RS-485.
When set to RS-422, the transm itter is always on. RS-
485 mode turns on the transmitter only when sending.

RS-422/485 OPERATING INFORMATION

RS-422/485 Termination network

When the RPC-320 is the last physical unit on a network
(RS-485), or it is the only unit (RS-422), the receiver
must be terminated to prevent ringing. Jumper block
W5, 6 installs or removes this network. Insert a jumper
in W5 and W6 to install the network terminator.

Only one slave device on a RS-485 network should have
a terminator installed. The host transmitter shou ld also
have a 100 ohm resistor in series with a 0.1 m fd
capacitor . T he term inator on the RPC -320 includes p ull
up and pull down resistors to prevent lines from floating
and generating er roneous char acters.