COMMERCIAL TANKLESS SERIES

MAXIMUM HOT WATER FLOW RATE AND TEMPERATURE RISE

Temp. Rise (°F)

35

45

50

60

70

77

90

100

110

120

130

140

Water Flow (GPM)

8.5

7.4

6.6

5.5

4.7

4.3

3.7

3.3

3.0

2.8

2.6

2.4

CLEARANCE TO
COMBUSTIBLES

(inches)

MODEL
NUMBER

SIDE REAR

GT-199PV

1/2

0

12

GT-199X

1/2

0

12

GT-199DV

1/2

0

12

Minimum flow rate required to initiate heating cycle .66 gpm.
Above estimates are for sizing purposes only.

FRONT

TOP &

BOTTOM

RHEEM-RUUD GT-199 MANIFOLD INSTALLATIONS

TEMP.

FLOW RATE (GPM)

RISE (°F)

1 UNIT

2 UNITS

5 UNITS

10 UNITS

15 UNITS

20 UNITS

140

2.4

4.7

11.9

23.7

35.6

47.4

130

2.6

5.1

12.8

25.5

38.3

51.1

120

2.8

5.5

13.8

27.7

41.5

55.3

110

3.0

6.0

15.1

30.2

45.3

60.3

100

3.3

6.6

16.6

33.2

49.8

66.4

90

3.7

7.4

18.4

36.9

55.3

73.7

80

4.1

8.3

20.7

41.5

62.2

83.0

77

4.3

8.6

21.5

43.1

64.6

86.2

70

4.7

9.5

23.7

47.4

71.1

94.8

60

5.5

11.1

27.7

55.3

83.0

110.6

50

6.6

13.3

33.2

66.4

99.6

132.7

45

7.4

14.7

36.9

73.7

110.6

147.5

35

8.5

17.0

42.5

85.0

127.5

170.0

Water Heater Flow Rate Curves

0

1

2

3

4

5

6

7

8

9

10

15

20

25

30

35

40

45

50

55

60

70

80

90

100

120

140

Delta-T

G

PM

Max Flow