Venting Arrangements - Horizontal

Terminations

This lightly shaded area of the diagram shows allowable combinations
of vertical runs with horizontal terminations, using one 45° and one
90° elbow
(two 45º

elbows equal one 90° elbow).

Note: Must use optional rigid pipe adapter (Part # 510-994) when

using Rigid Pipe.

Maintain clearances to combustibles.

Horizontal vent must be supported every 3 feet.

Firestops are required at each fl oor level and whenever passing
through a wall.

A vent guard may be required as per local codes, refer to Exterior
Vent Termination Locations.

Note: FPI Direct Vent System (Flex) is only approved for horizontal

terminations.

P33 Gas Fireplace

* Unit must be raised by 1” when using

Contemporary Faceplate

Please refer to Exterior Vent Terminations for

additional guidelines on vent locations.

35

August 2008 Product Specifi cations Book

Gas Fireplaces

Gas Fir

eplaces