RECOVERY CAPACITIES

Recovery in U.S. Gallons/Hr. (GPH) and Liters/Hr. (LPH) at Various Temperature Rises

INPUT

EQUIVALENT

40°F

50°F

60°F

70°F

80°F

90°F

100°F

110°F 120°F

130°F 140°F

KW

BTU/HR.

UNITS

(22°C)

(28°C)

(33°C)

(39°C)

(45°C)

(50°C)

(56°C)

(61°C)

(67°C)

(72°C)

(78°C)

6

GPH

LPH

9

30,709

GPH

93

74

62

53

47

41

37

34

31

29

27

LPH

352

282

235

201

176

157

141

128

117

108

101

12

40,946

GPH

124

99

83

71

62

55

50

45

41

38

35

LPH

470

376

313

268

235

209

188

171

157

145

134

15

51,183

GPH

155

124

103

89

78

69

62

56

52

48

44

LPH

587

470

391

335

294

261

235

213

196

181

168

18

61,420

GPH

186

149

124

106

93

83

74

68

62

57

53

LPH

705

564

470

403

352

313

282

256

235

217

201

24

81,893

GPH

248

199

165

142

124

110

99

90

83

76

71

LPH

939

751

626

537

470

417

376

342

313

289

268

30

102,366

GPH

310

248

207

177

155

138

124

113

103

95

89

LPH

1174

939

783

671

587

522

470

427

391

361

335

36

122,839

GPH

372

298

248

213

186

165

149

135

124

115

106

LPH

1409

1127

939

805

705

626

564

512

470

434

403

45

153,549

GPH

465

372

310

266

233

207

186

169

155

143

133

LPH

1761

1409

1174

1006

881

783

705

640

587

542

503

54

184,259

GPH

558

447

372

319

279

248

223

203

186

172

160

LPH

2114

1691

1409

1208

1057

939

845

769

705

650

604

ELECTRICAL CHARACTERISTICS

INPUT

KW

NO.

OF

ELE-

MENTS

ELE-

MENT

WAT-

TAGE

FULL LOAD CURRENT

IN AMPERES

208V

Phase

1 3

240V

Phase

1 3

600V

Phase

3

IMMERSION THERMOSTATS

Number

of Fuses

30A Class G

208/240V 600V

Number

of

Contactors

208/240V 600V

Optional Models – Staged

Models with Suffix “F”

Number of

Thermostats

KW Step

Size

Number

of

Thermostats

IMMERSION THERMOSTATS
Tank Capacity In Gallons

50 Gal. (190L) 85 Gal. (321L) 120 Gal. (454L)

EG50-C-9

EG85-C-9

EG120-C-9

EG50-C-12

EG85-C-12

EG120-C-12

EG50-C-15

EG85-C-15

EG120-C-15

EG50-C-18

EG85-C-18

EG120-C-18

EG50-C-24

EG85-C-24

EG120-C-24

EG50-C-30

EG85-C-30

EG120-C-30

EG50-C-36

EG85-C-36

EG120-C-36

EG85-C-45

EG120-C-45

EG85-C-54

EG120-C-54

INPUT

KW

6
9

12
15
18
24
30
36
45
54

N/A

ONE

THERMOSTAT

STANDARD

6

1

6

9

3

3000

43

25

38

22

9

6

3

2

1

1

9

12

3

4000

58

33

50

29

12

6

3

2

1

1

12

15

3

5000

72

42

63

36

15

6

3

2

1

1

15

18

3

6000

87

50

75

43

18

6

3

2

1

1

18

24

6

4000 116

67 100

58

23

12

6

4

2

1

2

12

30

6

5000 144

84 125

73

29

12

6

4

2

1

2

15

36

6

6000 173 100 150

87

35

12

6

4

2

1

2

18

45

9

5000 217 125 188 109

43

18

9

6

3

1

3

15

54

9

6000 260 150 225 130

52

18

9

6

3

1

3

18

MODEL NUMBERS