Mvb – type p, Model – Raypak MVB TYPE B 504-2004 User Manual

Page 2

Advertising
background image

Catalog No.: 6000.29B

Effective: 7-15-08

Replaces: 1-1-08

MVB – Type P

Models 504-2004

Model

Shown without H-bypass or Cold Water Run options

Dimensions (in.)

MBTUH

B

D

E

F

G

H

K

M

N

P

R V

Model

Input

Output

Height

NPT

NPT

Flue Ø

C/A Ø

Ship

Weight

(Lbs.)

Foot-

print

(Ft

2

)

Amps*

P-504

500

420

43

30

35

23-3/4

1

2

8

14-1/8

6

36

8

2

600

5.4

12

P-754

750

630

49

36

41

29-3/4

1

2

10

16

6

42

8

2

660

5.4

12

P-1104

1100

935

55

43

47

35-3/4

1-1/4

2-1/2

10

16

6

49

8

2

720

5.4

12

P-1504

1500

1275

61

50

53

41-3/4

1-1/4

2-1/2

12

18-1/8

8

53

8

2

780

5.4

12

WHP-2004

1900

1615

75

61

65

53-3/4

2

2-1/2

14

20-1/8

8

69

9

5

940

5.4

18

- Ratings shown are for elevations up to 4,500 feet. For installations at elevations

above 4,500 feet, please consult the factory for additional instructions.

* Current draw is for heater only.

(Supply breaker must have delayed trip.)

RATES OF FLOW

20°F

T

Minimum Flow

Maximum Flow

Model

GPM

P (ft.)

GPM

P (ft.)

T (°F)

GPM

P (ft.)

T (°F)

P-504

N/A

N/A

65

5.5

13

100

11.3

9

P-754

65

6.4

65

6.4

20

100

13.8

13

P-1104

94

13.6

85

11.5

22

113

18.6

17

P-1504

N/A

N/A

102

18.7

25

113

22.2

23

WHP-2004

N/A

N/A

102

22.7

32

113

27.2

29

Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (800) 872-9725 www.raypak.com

CLEARANCES

Certified

Minimum

Recomm.

Service

Front

24”

24”

Rear

12”

24”

Right

1”

Left

1”

Top

0”

10”

Floor

0”

Vent

1”

PUMP

Pump

Model

Model

HP

Amps*

P-504

1611

¼

6

P-754

1630

½

7

P-1104

1630

½

7

P-1504

1634

1

14

WHP-2004

1636

1 ½

22

* Current draw is for pump only

Advertising