INSTALLING THE VENT DAMPER

VENT DAMPER GENERAL WIRING DIAGRAM

Fig. # 8183.0

Fig. # 8615.0

NO

YES

NO

YES

INSTALL VENT

DAMPER WITH

ACTUATOR TO

SIDES OF VENT

ONLY. DO NOT

MOUNT ABOVE OR

BELOW VENT.

TO CHIMNEY

TO BOILER

D808

FLOW >

HORIZONTAL INSTALLATION

TO CHIMNEY

TO BOILER

D808

VERTICAL

INSTALLATION

ACTUATOR MAY BE

INSTALLED IN ANY

POSITION ON

VERTICAL PIPE.

VENT DAMPER

For safe, efficient operation, the vent damper and

all flue product carrying areas of the appliance must be
checked annually, with particular attention given to
deterioration from corrosion or other sources. Check
vent damper operation as follows:

1.

When the heater is off, check that the vent
damper position indicator points to the closed
position, Fig. 4.

INSTALL THE VENT DAMPER TO SERVICE ONLY THE SINGLE APPLIANCE FOR WHICH IT IS INTENDED.
IF IMPROPERLY INSTALLED, A HAZARDOUS CONDITION, SUCH AS AN EXPLOSION OR CARBON
MONOXIDE POISONING, COULD RESULT.

Fig. # 8181.0

2.

Turn the thermostat or controller up to call for heat
and check that the vent damper indicator points to
the open position, Fig. 4.

3.

Turn the thermostat or controller down again and
check that the vent damper position indicator
returns to the closed position.
THE VENT DAMPER MUST BE INSPECTED AT

LEAST ONCE A YEAR BY A TRAINED,
EXPERIENCED SERVICE TECHNICIAN. THE
NAME OF THE PERSON WHO ORIGINALLY
INSTALLED YOUR VENT DAMPER IS SHOWN ON
THE INSTALLATION LABEL.

DAMPER MUST BE IN

THE OPEN POSITION WHEN HEATER MAIN
BURNERS ARE OPERATING.

FIG. 4 - VENT DAMPER POSITON INDICATOR SHOWING OPEN & CLOSED POSITIONS.

Damper
Position
Indicator

DAMPER OPEN DAMPER CLOSED

Damper
Position
Indicator

16

HEATER

HEATER

Motor

End

Switch

C.

N.O.

N.C.

1K2

1K1

R

1R

1K3

1

2

3

4

5

D808

Thermostat or

Controller

Dual Valve

Combination Gas

Control or

Ignition System

Optional Limit

Location

Limit

Transformer

L1

(Hot)

L2

1

1

Yellow Blue

Power supply provide disconnect me

ans an overload protection as requ

ired.

Black Orange Red

Power supply provide disconnect means an overload protection as required.