Installing the water heater.

NOTICE: This guide recommends minimum branch circuit sizing and wire size based on National Electric Code.
Refer to wiring diagrams in this manual for field wiring connections.

Branch Circuit Sizing and Wire Size Guide

Total Water

Recommended Over Current Protection

Copper Wire Size AWG Based

Heater Wattage

(fuse or circuit breaker amperage rating)

on N.E.C. Table 310-16 (75°C)

208V

240V

277V

480V

208V

240V

277V

480V

3,000

20

20

15

15

12

12

14

14

4,000

25

25

20

15

10

10

12

14

4,500

30

25

25

15

10

10

10

14

5,000

30

30

25

15

10

10

10

14

5,500

35

30

25

15

8

10

10

14

6,000

40

35

30

20

8

8

10

12

8,000

50

45

40

25

8

8

8

10

9,000

50

45

25

8

8

10

10,000

50

30

8

10

11,000

50

30

8

10

12,000

35

8

Customer Service

T

roubleshooting Tips

Care and Cleaning

Operating Instructions

Installation Instructions

Safety Instructions

CAUTION: The presence

of water in the piping and
water heater does not
provide sufficient
conduction for a ground.
Non-metallic piping,
dielectric unions, flexible
connectors etc. can cause
the water heater to be
electrically isolated.

Electrical Connections

A separate branch circuit with copper
conductors, overcurrent protective device
and suitable disconnecting means must
be provided by a qualified electrician.

All wiring must conform to local codes
or latest edition of National Electrical
Code ANSI/NFPA 70.

The water heater is completely wired to
the junction box inside jacket at the top
front of the water heater. An opening for
1/2

or 3/4electrical fitting is provided

for field wiring connections.

The voltage requirements and wattage
load for the water heater are specified
on the rating plate on the front of the
water heater.

The branch circuit wiring should
include either:

Metallic conduit or metallic
sheathed cable approved for use as
a grounding conductor and
installed with fittings approved for
the purpose.

Non-metallic sheathed cable,
metallic conduit or metallic
sheathed cable not approved for
use as a ground conductor shall
include a separate conductor for
grounding. It should be attached to
the ground terminals of the water
heater and the electrical
distribution box.

WARNING

WARNIN

G

Water heater junction box.

Ground screw

Junction

box

cover

Wire connections

Conduit

connector

Advertising