The pressure rating of the relief valve must not exceed 150 psi

(1,034 kPa), the maximum working pressure of the water heater
as marked on the rating plate. The BTUH Rating of the relief valve
must not be less than the input rating of the water heater as in-
dicated on the rating label located on front of the heater
(1 watt = 3.412 BTUH).

Connect the outlet of the relief valve to a suitable open drain so that the
discharge water cannot contact live electrical parts and to eliminate
potential water damage. Piping used should be of a type approved for
hot water distribution. The discharge line must be no smaller than the
outlet of the valve and must pitch downward from the valve to allow
complete drainage (by gravity) of the relief valve and discharge line. The
end of the discharge line should not be threaded or concealed and
should be protected from freezing. No valve of any type, restriction or
reducer coupling should be installed in the discharge line.

4. TO FILL WATER HEATER —

Make certain drain valve is completely

closed. Open shut-off valve in cold water supply line. Open each hot
water faucet slowly to allow air to vent from the water heater and piping.
A steady flow of water from the hot water faucet(s) indicates a full water
heater.

Tank MUST BE full of water before power is turned on. Heating
element(s) WlLL BE DAMAGED if energized for even a short time
while tank is dry. The water heater’s warranty does not cover
damage or failure resulting from operation with an empty or
partially empty tank. (Reference is made to the limited warranty for
complete terms and conditions.)

5. ELECTRICAL CONNECTIONS —

A separate branch circuit with copper

conductors, overcurrent protective device and suitable disconnecting
means must be provided by a qualified electrician. All wiring must
conform to local codes or the latest edition of National Electrical Code
ANSI/NFPA 70, or in Canada, the Canadian Electric Code.

In order to conform with U.L. requirements, it is

absolutely necessary

that the Junction Box Kit be installed per figure 3 above. An opening for
either 1/2” or 3/4” electrical fitting is provided for field wiring connections.
Refer to Figure 3.
The voltage requirements and wattage load for the water heater is
specified on the rating plate on the front of the heater.
Table 1, below, recommends minimum branch circuit sizing based on
the National Electric Code. Refer to the wiring diagram marked on the
back cover of this manual for field wiring connections.

Installation

R

E

L

I

E

F

V

A

L

V

E

COL

D

HO

T

Heat trap

6" (15.24 cm)

minimum

6" (15.24 cm)

air gap

Union

Temperature

&

Pressure

Relief Valve

Anode

Union

Hot

water outlet

to fixtures

Jacket access

panels

Drain valve

Auxiliary

catch pan

2" (5 cm)

maximum

Relief valve

discharge line to

suitable open drain

Thermal

expansion tank

(if required)

Electrical

junction box

(use only copper

conductors)

To

cold water

supply

Shut-off

valve

Heat trap

6" (15.24 cm)

minimum

Figure 2. — Typical Installation

WARNING

!

WARNING

TANK MUST BE FULL

OF WATER BEFORE

HEATING ELEMENTS

ARE ENERGIZED. SEE

INSTALLATION

INSTRUCTIONS

Figure 3. — Water Heater Junction Box.

Table 1. — Branch Circuit Sizing and Wire Size Guide Based on

N.E.C. ANSI / NFPA 70

P

Recommended Over

Total

h

Current Protection

Copper Wire Size -

Water

a

(Fuse or Circuit Breaker)

AWG Based on N.E.C.

Heater

s

Amperage Rating

Table 310-16 (75°C.)

Wattage

e

208V

240V

277V

480V

208V

240V

277V

480V

3,000

1

20

20

15

15

12

12

14

14

3

20

20

---

15

12

12

---

14

4,000

1

25

25

20

15

10

10

12

14

3

25

25

---

15

10

10

---

14

4,500

1

30

25

25

15

10

10

10

14

3

30

25

---

15

10

10

---

14

5,000

1

30

30

25

15

10

10

10

14

3

30

30

---

15

10

10

---

14

5,500

1

35

30

25

15

8

10

10

14

3

35

30

---

15

8

10

---

14

6,000

1

40

35

30

20

8

8

10

12

3

35

30

---

15

8

10

---

14

8,000

1

50

45

40

25

8

8

8

10

3

45

40

---

20

8

8

---

12

9,000

1

---

50

45

25

---

8

8

10

3

50

45

---

25

8

8

---

10

10,000

1

---

---

50

30

---

---

8

10

3

---

50

---

25

---

8

---

10

11,000

1

---

---

50

30

---

---

8

10

3

---

50

---

25

---

8

---

10

12,000

1

---

---

---

35

---

---

---

8

3

---

---

---

30

---

---

---

10

Three (3) sheet metal screws removed
from "factory installed" junction box.

Cover and Label

Insert Electrical Leads
through Snap Bushing into
Junction Box

Leads from water heater.
Either 2, 3 or 4 wires

Snap

Bushing

Ground

Screw

Vacuum Relief Valve

(Not Supplied)

If required, install per local codes

and valve manufacturer’s

instructions.

Advertising