Model LP Dry Valve Actuator Parts List
P/N 71030010

Refer to Fig. 8

16.

Note:

For metric installations, a 2" NPT x R2, ISO 7/1 x Close Nipple (Reliable P/N 98543401) is sold separately as an

adapter for the single drain outlet of the trims.

Ordering Information

Specify
Valve Model & Size

— 4”(100mm) Model DDX Deluge Valve (P/N 6103040026), 6”(150mm) Model DDX Deluge Valve

(P/N 6103060024), 165mm Model DDX Deluge Valve (P/N 6103060028).

Trim

— The trim set is available in individual parts, in time-saving segmentally assembled kit forms, or fully assembled

to the Model DDX Deluge Valve.

Item

No.

Part No.

Description

Qty.

Required

1

94106936

Lower Housing

1

2

94106935

Upper Housing

1

3

96006905

Seat

1

4

92206311

Diaphragm

1

5

95106911

Facing Plate Assembly

1

6

96906311

Diaphragm Washer

1

7

94906406

Facing Plate Nut

1

8

95406901

Seat O-Ring

1

9

95606305

Bolt

6

10

96406902

Compression Spring

1

Trim Configurations

Trim Part Numbers

4" (100mm) Valve

6" (150mm) Valve

165mm Valve

Fully Assembled to Model DDX Valve

6505040400

6505060400

6505065400

Segmentally Assembled

(Model DDX Valve Sold Separately)

6502071710

Individual Parts

(Model DDX Valve Sold Separately)

6502071700

Maintenance – Model LP Dry Valve Actuator

Refer to Figs. 7 and 8

1. If water constantly flows through the Model LP Dry

Valve Actuator and into the drain, there is a leak in the
seal of the Actuator’s seat.

2. Close the main valve controlling water supply (Fig. 7) to

the Deluge Valve and close off the air/nitrogen supply
to the sprinkler system. Close valve A (Fig. 7).

3. Drop pressure in the system by opening the ¼” angle

valve, valve E (Fig. 7), and remove the Actuator from
the system.

4. Remove all six bolts (#9, Fig. 8) holding the Actuator to-

gether. Clean or replace the facing plate assembly (#5,
Fig. 8) and seat (#3, Fig. 8).

5. Reassemble the Actuator, using a torque of 8 ft-lbs on

the facing plate nut (#7, Fig. 8) and 12 ft-lbs on the six
bolts (#9, Fig. 8). Use a cross-tightening pattern. Rein-
stall the Actuator. Set up the Model DDX Deluge Valve
as per the section of this bulletin entitle “Resetting the
Single Interlock Preaction System.”