Type h - hydronic heating, Model – Raypak 122-322 User Manual

Page 2

Advertising
background image

Catalog No.: 2000.18C

Effective: 11-15-07

Replaces: 7-15-05

Hi Delta 122-322

Type H - Hydronic Heating

Model


OPTIONAL ELECTRICAL CONNECTION

OPTIONAL GAS CONNECTION

K

COMBUSTION AIR

11

10-3/8

16-3/4

LEFT SIDE

3-3/4

8-1/2

15-13/16

ELECTRICAL CONNECTION

GAS CONNECTION 3/4"

13-3/4

WATER OUT

H

T

FRONT

WATER IN

H

TOP

A

FLUE CONNECTION

18

7-15/16

B

19-3/4

RIGHT SIDE

26-1/8

OPTIONAL PUMP COVER

OPTIONAL PUMP

(11.22)

(9.35)

PUMP LOCATION AND ORIENTATION

MAY VARY WITH UNIT CONFIGURATION



APPROX.

MBTUH

AFUE FIRING

A

B

H K T SHIP

WT.

MODEL INPUT OUTPUT (%) STAGES

NPT

(LBS.)

H 122

120

101

84

2* 24-7/8

10-3/4

1-1/4

4

5 225

H 162

160

134

84

2* 28-1/2

12-9/16

1-1/4

5

5 240

H 202

199

167

84

2* 32-1/8

14-3/8

1-1/4

5

5 255

H 242

240

202

84

2* 35-1/2

16-3/16

1-1/2

5

5 270

H 322

320

269

N/A

2* 42-5/8

19-13/16 1-1/2

6

5 300

Dimensions are in inches.

* 1 stage optional

RATES OF FLOW AND PRESSURE DROPS

10ºF

T 20ºF

T 30ºF

T

MIN. FLOW

MAX. FLOW

MODEL GPM

P (ft) GPM P (ft) GPM P (ft) GPM P (ft) T GPM P (ft) T

H 122

20

2.5

10 <1.0 N/A N/A 10 <1.0

20

30 5.3 7

H 162

27

4.5

13 1.1 N/A N/A 10 <1.0

27

30 5.4 9

H 202

34

7.2

17 1.85 11 <1.0 10

<1.0

34

30 5.5 11

H 242

40

10.0

20 2.65 14 1.3 10

<1.0

40

44 11.8 9

H 322

N/A

N/A

27 4.7 18 2.2 14 1.35 40

44 12.2

12

Basis is 10 GPM or 40°F

∆T for minimum flow, 44 GPM for maximum flow (except for 1.25” header).


NOTES: 1. Rates shown are for natural or propane gas, and elevations up to 5,000 feet. For installations above 5,000 feet, please contact manufacturer.

2. Recommended natural gas pressure is 7 – 10.5” WC. Recommended propane gas pressure is 11 - 13” WC.

Raypak, Inc.

ƒ 2151 Eastman Avenue, Oxnard, CA 93030 ƒ (805) 278-5300 ƒ Fax (800) 872-9725 ƒ www.raypak.com

Advertising