Roberts Gorden GordonRay BH-40 User Manual

Page 14

Advertising
background image

BH-S

ERIES

I

NSTALLATION

, O

PERATION

AND

S

ERVICE

M

ANUAL

8

NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.

2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.

FIGURE 12: Venting

(inches)

(centimeters)

Model

A

E

F

A

E

F

BH-40

14

18

18

36

46

46

BH-60

14

18

18

36

46

46

BH-80

20

24

18

51

61

46

BH-100

20

24

18

51

61

46

BH-115/125

20

24

18

51

61

46

BH-140/150

20

30

18

51

77

46

BH-175/200

20

30

18

51

77

46

Radiant Tubes

Vent

Pipes

Unvented

Vented

A

E

F

Advertising