Division 23 52 33.13 - 1


DIVISION 23 52 33.13

FINNED WATER-TUBE WATER HEATERS

PART 1 - GENERAL

1.1 SUMMARY

A. Section includes gas-fired, copper finned-tube water heaters for use with a storage tank.
B. Related

Sections

Specifier Note: Use as needed
1. Building Services Piping – Division 23 21 00
2. Breeching, Chimneys, and Stacks (Venting) – Division 23 51 00
3. HVAC Instrumentation and Controls – Division 23 09 00
4. Electrical – Division 23 09 33

1.2 REFERENCES

A. ANSI Z21.10.3/CSA 4.3
B. ASME, Section IV
C. 2006 UMC, Section 1107.6
D. ANSI/ASHRAE 15-1994, Section 8.13.6
E. National Fuel Gas Code, ANSI Z223.1/NFPA 54
F. NEC

1.3 SUBMITTALS

A. Product data sheet (including dimensions, rated capacities, shipping weights, accessories)
B. Wiring

diagram

C. Warranty information
D. Installation and operating instructions

1.4 QUALITY

ASSURANCE

A. Regulatory

Requirements

1. ANSI Z21.10.3/CSA 4.3
2. Local and national air quality regulations for low NOx (<20 PPM NOx emissions) water heaters

B. Certifications

1. CSA
2. ASME HLW Stamp and National Board Listed

1.5 WARRANTY

A. Limited five-year warranty from date of installation
B. Limited twenty-year thermal shock warranty from date of installation
C. Limited ten-year warranty for cupro-nickel heat exchangers only

PART 2 - PRODUCTS

2.1 MANUFACTURER

A. Raypak,

Inc.

1. Contact: 2151 Eastman Ave., Oxnard, CA 93030; Telephone: (805) 278-5300;

Fax: (800) 872-9725; Web site: www.raypak.com

2. Product: HD™ copper finned-tube water heater(s)

2.2 WATER

HEATERS

Hi Delta SS™, TYPE WH - MODELS HD101 – HD401

SUGGESTED SPECIFICATIONS

Catalog No.: 3500.961A
Effective: 12-29-09
Replaces: 6-25-09