Raypak B0109 User Manual

Page 13

Advertising
background image

INSTALLATION

13

CLEARANCES (INDOOR INSTALLATIONS)

The distances set out in the following table should be observed.

109

Models

Minimum

Clearances from:

Non-Combustible

materials (mm)

Combustible

materials (mm)

Rear 150 500

Water Side

300

600

Front 750 750

Non Water side

150

500

Ceiling 1200 1200

147

Models

Minimum

Clearances from:

Non-Combustible

materials (mm)

Combustible

materials (mm)

Rear 300 500

Left side

300

500

Front 750 750

Right side

300

500

Ceiling 1200 1200

The normal water heater design is with the water pipe entry from the left hand side on 109 models and the rear for
147 models. For servicing purposes allow at least 750mm in front of the water heater for burner tray removal.

COMBUSTION / VENTILATION AIR

Indoor model water heaters must be installed in a protective enclosure or properly constructed plant room with
adequate ventilation in accordance with AS 5601.

Ideally ventilation shall be via two permanent openings DIRECTLY to outside, one at an upper level and one at low
level.

Where the air is sourced DIRECTLY from outside the minimum free area
required for each opening is provided in the table opposite. Where the
ventilation is by an alternate method refer to AS 5601 for ventilation
calculations.

NOTE:

The minimum dimension of any opening shall be 6mm

WARNING!

Air supply to the area where the water heater is installed must not be affected by mechanical

exhaust vents such as kitchen or bathroom fans, spa blowers, etc. Mechanical exhaust vents may create a
negative pressure in the area where the water heater is installed and can become a hazard by asphyxiation,
explosion or fire.

SAFE TRAY

It is a requirement of AS/NZS 3500.4 that for a new installation, a water heater be installed in a safe tray where in
the event of a leak, property may otherwise be damaged. Construction, installation and draining of a safe tray must
comply with the abovementioned Standard. The safe tray must NOT restrict combustion airflow.

OUTDOOR INSTALLATION

For servicing allow at least 750 mm in front of the water heater for burner
removal and 450 mm on the water connections side for heat exchanger
servicing.

The water heater must NOT be installed inside any roofed structure or under
eaves, roof overhangs, or pool decks.

When installing the water heater on a raised base, the base material MUST be
solid and filled in (e.g. if steel mesh decking is used, a suitable plate material

Model

Total area (cm

2

)

109 327

147 441