Raypak WH & P L W User Manual

Page 30

Advertising
background image

30

speed. Do not operate summer exhaust fan. Close

fireplace dampers.

4.

Place in operation the appliances being inspected.
Follow the manufacturer’s instructions for lighting
each appliance. Adjust thermostat so appliance
will operate continuously.

5.

Check the pressure at a pressure tap located 12
in. above the bottom joint of the first vertical vent
pipe. Pressure should be anywhere between -0.01
and -0.08 in. WC.

6.

After it has been determined that each appliance
remaining connected to the common venting sys-
tem properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace
dampers and other gas burning appliances to their
previous conditions of use.

7.

Any improper operation of the common venting
system should be corrected so that the installation
conforms with the NFGC (U.S.) or B149.1
(Canada). When re-sizing any portion of the com-
mon venting system, the common venting system
should be re-sized to approach the minimum size
as determined using the appropriate tables in the
NFGC (U.S.) or B149.1 (Canada).

Horizontal Through-the-Wall Venting
(Category III)

Installation

These installations utilize the heater-mounted blower
to vent the combustion products to the outdoors.
Combustion air is taken from inside the room and the
vent is installed horizontally through the wall to the out-
doors. Adequate combustion and ventilation air must
be supplied to the equipment room in accordance with
the NFGC (U.S.) or B149.1 (Canada).