R90 Wood Fireplace

Model

R90

Emissions

3.72 g/hr

Effi ciency (EPA)

63%

BTU/h (EPA)

11,720 (Low) to 42,400 (High)

Flue Size

8” (203mm) Diameter

Log Size

20” (508mm)

Shipping Weight

612 lbs. (278 kg)

Stripped Weight

570 lbs (259 kg)

C

A

E

B

D

F

Unit Dimensions Description

R90

A

Unit Width w/ standoffs

43-5/8” (1108mm)

B

Unit Height w/ standoffs

50-1/2” (1283mm)

C

Unit Width

38” (965mm)

D

Unit Height

42-5/8” (1067mm)

E

Unit Depth w/ standoffs

28” (711mm)

F

Unit Depth

25” (635mm)

Framing
Dimensions

Description

R90

USA Only

Canada Only

G

Framing Width

44” (1118mm)

44” (1118mm)

H

Framing Height

50-3/4” (1289mm)

50-3/4” (1289mm)

I

Framing Depth

28” (710mm)

28” (710mm)

J

Corner Wall Length

68” (1729mm)

81-1/2” (2072mm)

K

Corner Facing Wall Width

96-1/4” (2445mm)

115-3/8” (2930mm)

L

Inside Corner to Center Vent

24-1/2” (624mm)

31-1/4” (795mm)

M

Unit Corner Clearance

3” (76mm)

9-3/4” (248mm)

N

Inside Chase Framing Width

44” (1118mm)

60” (1524mm)

O

Hearth

**

Depth

18” (457mm)

18” (457mm)

P

Hearth

**

Width

40” (1016mm)

40” (1016mm)

Q

Thermal Protection Thickness

1/2” (12.7mm)

1/2” (12.7mm)

R

Combustible Ceiling Height

84” (2134mm)

84” (2134mm)

**

Required Non-combustible Hearth with thermal protection - Minimum
“K” Factor of 20.07 (CAN) or 0.84 (US)

171

June 2007 Regency Product Specifi cations Book

Wood Fireplaces

W
ood Fir

eplaces

Finishing Material

Safety Strip

Z Type

Safety Strip

Finishing

Material

2-1/2”

(64mm)

2-1/2” (64mm)

G

H

I

K

J

L

M

O

P

N

P

O

N

USA ONLY

CANADA ONLY

R

Q

Q

Thermal Protection

Thermal

Protection

NOTE: Hearth requires thermal protection in front of the fi replace and

must have at least 1/2" (13mm) Millboard under the fi nishing
material with minimum "k" factor of 20.07 (in Canada), 0.84 (in
US). If the bottom of the unit is raised 4" (102mm) above the
hearth, the thermal fl oor protection is not required.

NOTE: Safety strip is required when the fi replace rests on a combustible

surface, and should extend 2” in front and on the sides of the
fi replace. When using a wooden support to raise the fi replace.
A “Z” type safety strip, not supplied, must be fabricated (Use 20
gauge galvanized sheet steel).