Installation, Exterior vent termination locations – Regency Panorama P36D User Manual

Page 20

Advertising
background image

FPI P36D-1 Zero Clearance Direct Vent Gas Fireplace

20

EXTERIOR VENT TERMINATION LOCATIONS

A= Clearance above grade, veranda, porch, deck, or balcony *(min.

12"/30cm)

B= Clearance to window or door that may be opened *(12"/30cm)
C= Clearance to permanently closed window *(min. 12"/30cm)
D= Vertical clearance to ventilated soffi t located above the terminal

within a horizontal distance of (24"/60cm) from the centerline of
the terminal (min. 18"/46cm) check with local code.

E= Clearance to unventilated soffi t (min. 15"/38cm)
F= Clearance to outside corner: with AstroCap Termination Cap (min.

6"/15cm), with Dura-Vent Termination Cap (14"/36cm)

G= Clearance to inside corner: with AstroCap Termination Cap (min.

6"/15cm), with Dura-Vent Termination Cap (12"/30cm)

H= Not to be installed above a meter/regulator assembly within (3'/90cm)

horizontally from the centerline of the regulator.

J= Clearance to service regulator vent outlet *(min. 36"/90cm)
K= Clearance to non-mechanical air supply inlet to building or the com-

bustion air inlet to any other appliance *(12"/30cm)

L= Clearance to a mechanical air supply inlet *(min. 72"/1.8m)
M= Clearance above paved sidewalk or a paved driveway located on

public property *(min. 84"/2.1m)

N= Clearance under veranda, porch, deck, or balcony *(min.

12"/30cm)

Note:
- A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both
dwellings.
- Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor.
- If the vent termination is accessible, a certifi ed guard shall be installed.
* As specifi ed in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances.