Installation, Test for flue spillage, Gas insert aeration system – Regency E21-LP1 User Manual

Page 11: Optional brick panel

Advertising
background image

11

Regency E21 Gas Fireplace Insert

INSTALLATION

TEST FOR

FLUE SPILLAGE

A " spillage" test must be made before

the installed unit is left with the customer.

Follow the procedure below:

1) Close all external doors and windows in

the house.

2) Light the unit and set controls to maximum.

Turn fan to OFF on unit.

3) After fi ve minutes, test that there is a “pull”

on the fl ue by placing a smoking match,

cigarette or similar device which gives

off smoke, in front of the upper part of

the louver. To ensure a valid test, place

GAS INSERT AERATION

SYSTEM

The aeration adjustment rod is attached to the

air shutter which is located just above the orifi ce

bracket. The rod is used to adjust the aeration

on the main burner without having to take the

appliance apart.

The burner aeration is factory set but may need

adjusting due to either the local gas supply, air

supply or altitude.

Natural Gas: 1/8" (3.2mm) open

Propane:

3/16" (4.8mm) open

Note: Any damage due to carboning

resulting from improperly setting

the aeration controls is NOT covered

under warranty.

Note: Aeration Adjustment should only be

performed by an authorized Regency

Installer at the time of installation or

service.

a scrap piece of sheet metal (or other

noncombustible material) in the upper louver,

this will prevent the natural convection of the

unit from interfering with the test.

Note: The smoke should be drawn into the

louver. If the smoke is still not drawn

in, turn the unit off and check for the

cause of the lack of draft. If necessary,

seek expert advice.

OPTIONAL

BRICK PANEL

1) Unwrap the brick pattern panels from the

protective wrapping.

2) With the glass removed, position the

back panel fi rst (see diagram for correct

positioning), then the two side panels. Slide

the side brick panel into place from the front

of the fi rebox, there is a tab at the top of the

unit to hold the side panels in place.

3) The brick panels should be tight against

the fi rebox sides and back. The side panels

should be fl ush with the glass.

Note: Use caution when sliding side panels

in as they can easily be scratched by

the brick panel tabs.

Valve Description

1) Gas cock knob
2) Manual high/low adjustment
3) Pilot Adjustment
4) Thermocouple Connection
5) Main Operator
6) Outlet Pressure Tap (Manifold Pressure)
7) Inlet Pressure Tap (Supply Pressure)
8) Pilot Outlet
9) Main Gas Outlet
10) Flange Securing Screw Holes
11) Alternative TC Connection Point
12) Thermoelectric Unit
13) Additional Valve Mounting Hole