Figure 16: Automatic Burner Control Sequence

Figure 17: Gas Valve for Models UHA[X][S] 30 - 45

Burner Sequence for Ignition Control

Flame Signal

Start Gas Valve

Ignition Spark

Thermostat 24 V

SHUT DOWN

RUN

START

ts = 10 Seconds

Signals Output By Control

Required Incoming Signals

Flue Blower

Pressure

Switch

P

C

NO

NC

30 Seconds Purge*

*Purge time begins at pressure switch change over.

Axial Fan

30 Seconds Delay

90 Seconds Delay

30 Seconds Post Purge

If at any stage the flame fails, the control will retry
for ignition. The control has four trials for ignition
before a one hour lockout.

Pressure Regulator

Gas Outlet

Outlet Pressure

Description

Part Number

Gas Valve 30 - 45 NG

90034500

Gas Valve 30 - 45 LP

90034600