Water connections – Rheem Indirect Water Heater User Manual

Page 9

Advertising
background image

BOILER

SYSTEM

SUPPLY

CIRCULATOR

PUMP

BOILER

SYSTEM

RETURN

BOILER

COLD

1"

INLET

WATER HEATER

INDIRECT

HOT OUT

DOMESTIC

1 1/2"

BOILER

FROM

TO

BOILER

CHECK

VALVE

BOILER

SUPPLY

SYSTEM

DOMESTIC

3/4"

HOT OUT

INDIRECT

WATER HEATER

BOILER

TO

BOILER

FROM

COLD

INLET

3/4"

VALVE

CHECK

PUMP

CIRCULATOR

RETURN

SYSTEM

BOILER

BOILER

1" NPT

1" NPT

1" NPT

1" NPT

BOILER

SYSTEM

SUPPLY

CIRCULATOR

PUMP

BOILER

SYSTEM

RETURN

BOILER

COLD

1"

INLET

WATER HEATER

INDIRECT

HOT OUT

DOMESTIC

1 1/2"

BOILER

FROM

TO

BOILER

CHECK

VALVE

BOILER

SUPPLY

SYSTEM

DOMESTIC

3/4"

HOT OUT

INDIRECT

WATER HEATER

BOILER

TO

BOILER

FROM

COLD

INLET

3/4"

VALVE

CHECK

PUMP

CIRCULATOR

RETURN

SYSTEM

BOILER

BOILER

1" NPT

1" NPT

1" NPT

1" NPT

Page 9

Figure 7: STID80, STID120 water connections

SECTION IV: INSTALLATION

WaTer ConneCTIons

All piping between the boiler and the indirect water heater should be new copper with a
minimum size of 3/4” ID for models STID30, STID40, and STID50. Use 1” minimum copper for
models STID80 and STID120. Elbows should be minimized. A flow check valve must be
installed on the return line.

All piping to the inlet (cold) and outlet (hot) domestic water connections should be new copper
with a minimum size of 1/2” ID for models STID30, STID40, and STID50. Use 3/4” ID minimum for
models STID80 and STID120.

All piping should conform to local codes and ordinances. At a minimum, refer to ILHR 84 code if
local codes are not in place. It is recommended that all piping be adequately insulated with
approved material to ensure minimum heat loss. If a re-circulation line is used for domestic
water, be certain that all lines are well insulated and the circulator is temperature controlled.
Install isolation valves to permit proper servicing. It is also recommended to install a union on
the domestic outlet to facilitate replacement of the hot outlet / anode nipple on models STID30,
STID40, and STID50.

See Figures 6 and 7 for proper water connection installation.

NOTICE: Indirect water heater may be connected to a steam
boiler provided that all piping to and from
the boiler are below the water line of the boiler.
Boiler must also be protected by a low water
cut off safety device.

Figure 6: STID30, STID40, STID50 water connections

Advertising