Raypak RAYTHERM 2100 User Manual

Raytherm, Type wh, Water heaters commercial

Advertising
background image

Catalog No.: 3500.24C

Effective: 08-10-11

Replaces: 01-15-08

Job:

Engineer:

Contractor:

Prepared By:

Model:

Indoor Date:

EFFICIENT


82% thermal efficiency – highest of any atmospheric

water heater available today

THERMAL SHOCK PROOF


Twenty-year warranty against thermal shock damage

up to 150°F differential



Maximum outlet temperature: 210°F

LIGHTWEIGHT


A floor load of 70 lbs./sq. ft. or less

HIGH RECOVERY


Cuts fuel costs substantially because the standby

and radiation losses associated with tank-type
water heaters are eliminated

LOW WATER OPERATING TEMPERATURE


Operates with water temperature as low as 105°F

without condensing

Heat Exchanger
ƒ

ASME Inspected and Stamped
160 PSIG

ƒ

National Board Approved

ƒ

Headers

Bronze – Standard
Glass-lined Cast Iron – Option A-2

ƒ

Fin

Tubing

Copper – Standard
Cupro Nickel – Option A-3

ƒ

ASME Steel Tube Sheet

ƒ

Silicone

O-Rings

ƒ

125 PSIG ASME Pressure Relief Valve

ƒ

Temperature and Pressure Gauge

ƒ

Water

Connections

Left Hand – Standard
Right Hand – Option A-6

ƒ

Two-pass Flow Configuration

Controls
ƒ

120V, 60Hz, 1 Ph Power Supply

ƒ

120/24V

Transformer

ƒ

100% Pilot Shut-off/Lockout

ƒ

Electronic,

Intermittent Ignition (IID) Pilot

ƒ

High Limit Control, Manual Reset – 200°F

ƒ

High Limit Control, Auto Reset – 200°F
Models 3001-4001

ƒ

On/Off

Switch

ƒ

Flow

Switch

ƒ

Economaster II Pump Time Delay

Gas Control Train
ƒ

Manual Main Gas Shut-off Valve

ƒ

Main Gas Pressure Regulator

ƒ

Redundant Safety Shut-off Valve

ƒ

Control Valve

ƒ

Firing

Mode

On/Off (WH1)
2-stage Firing (WH3)
Motorized Modulation (WH2)

ƒ

Fuel

Natural Gas
Propane Gas

ƒ

Design Certified ANSI Z21.10.3

Construction
ƒ

Front

Controls

ƒ

Stainless Steel Burners

ƒ

Baked Enamel Paint

ƒ

Built-in Draft Diverter

ƒ

Draft Inducer – Optional

Motorized Draft Inducer –

Indoor – Option D-2

ƒ

CSA Certified – AB 1953 & VLA 193
Low Lead Compliant



Water Heater Controller
Required on Model WH2 only

B-40 TempTracker MOD

Modulating

Controller

Mounted

By Others

Temperature Controllers

B-2

Single-Stage Tankstat
(100-180°F), Loose

B-3

2-Stage Tankstat (100-180°F),
Loose

Y-241 Electronic Sequencer,

1-4 Stages

Y-281 Electronic Sequencer,

1-8 Stages

Additional Safety Controls

F-9

Low Water Cut-off Probe

I-3

High Limit Control, Auto Reset,
180°F

S-1

Low Gas Pressure Switch,
Manual

S-2

High Gas Pressure Switch,
Manual

Regulatory Agency Requirements

CSD-1

Safety

Controls

Raytherm

®

- Type WH

Water Heaters

Commercial

Models 2100 - 4001

Proudly Made in the USA

Advertising