Hi delta flexgas – type h, Model – Raypak 302BD-902BD User Manual

Page 2

Advertising
background image

Catalog No.: 2000.303A

Effective: 11-15-07

Replaces: 8-15-07

Hi Delta FlexGas – Type H

Models 302BD-902BD

Model

RATES OF FLOW AND PRESSURE DROPS

10°F

T 20°F

T 30°F

T

Min. Flow

Max. Flow

Model GPM

P (ft) GPM P (ft) GPM P (ft) GPM P (ft) T GPM P (ft) T

302BD 51 3.2 25 <1.0 N/A N/A 20 <1

25

90

9.8

6

402BD

68 5.4 34 1.5 22 <1 20 <1 34 90 10.0 7

502BD

85 9.2 42 2.3 28 1.1 21 <1 40 90 10.5 9

652BD

N/A N/A 55 4.0 36 1.8 28 1.1 40 90 10.7

12

752BD

N/A N/A 64 5.5 42 2.5 32 1.6 40 90 11.0

14

902BD

N/A N/A 76 8.5 51 3.8 38 2.2 40 90 11.8

17

Basis is 20 GPM or 40°F

∆T for minimum flow, 90 GPM for maximum flow.

NOTE: Pump location
varies based on model
and application

SPECIFICATIONS

Approx.

MBTUH

A

B

G

H

K T W Amp. Shipping

Model Input Output Width

Nat

Pro NPT

Draw* Wt.

(Lbs)

302BD

300

252

36

41

1-1/4

3/4

2 5

6 18 6

405

402BD

399 335 43 41

1-1/4

3/4

2 6

6

18-1/2

6

470

502BD

500 420 50 35-1/2 1-1/4

3/4

2 6

6 22 6

570

652BD

650 546 60-1/2 30-1/2 1-1/4

3/4

2 8

6

27-1/4

6

615

752BD

750 630 67-1/2 27-1/2 1-1/4 1-1/4

2 8

6

30-3/4

6

700

902BD

900 756 78 34-1/2 1-1/4 1-1/4

2 8

6 36 7

765

* Without pump

NOTES:

1. Dimensions are in inches

2. Rates shown are for natural or propane gas, and

elevations up to 5,000 feet. For installation above
5,000 feet, please contact manufacturer.

3. Required natural gas supply pressure is 7 - 10.5” WC.

Required propane gas supply pressure is 11 - 13” WC.

Raypak, Inc.

ƒ 2151 Eastman Avenue, Oxnard, CA 93030 ƒ (805) 278-5300 ƒ Fax (800) 872-9725 ƒ www.raypak.com

Advertising