Wood stoves, Minimum alcove clearance to combustible materials, Floor protection – Regency H300 User Manual

Page 2: Additional clearances for backwall exit

Advertising
background image

98

June 2007 Hampton Product Specifi cations Book

W

ood Sto

v

es

Wood Stoves

H300 Wood Stove

Unit

(with heat Shield)

From Unit

From Vent

centerline

Min.

Width

Min. Hearth

to Rear Wall

G

H

I

J

K

L

H300 (with side load
door)

15”

13”

28”

13”

60”

51-1/4”

H300 (without side
load door)

15”

13”

28”

13”

57”

51-1/4”

Minimum Alcove Clearance To
Combustible Materials

Hampton Freestanding models have been alcove approved and must be
installed with a listed double wall connector to the ceiling level.

Note: Minimum alcove ceiling height - 60"

Maximum depth of alcove - 48"

*The rear clearance to combustibles is less than 6" (152mm), for corner
installations the rear corners may be angled to take advantage of the
closer clearances.

NOTE: In Canada, fl oor protection must extend 18" to the front

and 8" to each side of the stove.

Floor Protection

A combustible fl oor must be protected by a non-combustible material
(like tile, concrete board, or certifi ed to UL-1618 or as defi ned by local
codes) extending beneath the heater and a minimum of 6" from each
side and minimum 18" from the front face of the stove and minimum 6"
(or the rear clearance to combustibles whichever is smaller) from the
rear of the stove.
When installed with horizontal venting, non-combustible fl oor protection
must be installed underneath the fl ue pipe and extend 2" (51mm) beyond
each side.

Minimum Overall Width (X) of Floor
Protector
for all installations:

H300 (US)

39"

H300 (Canada)

43”

Minimum Overall Depth (Y) of Floor Protector

Unit

Residential

“C” Vent

Residential

Close

Clearance

Mobile

Home Close

Clearance

Alcove

Y

Z

Y

Z

Y

Z

Y

Z

H300 (US)

44-1/2”

6”

44-1/2”

6”

44-1/2”

6”

44-1/2”

6”

H300 (Canada)

46-1/2”

8”

46-1/2”

8”

46-1/2”

8”

46-1/2”

8”

Mobile Home Close Clearance

(To be installed with required pipe components)

“C” Vent single wall pipe is not approved for Mobile Home installations. (Refer to mobile home instructions.)

Unit

(with heat Shield)

From Unit

From Corner

From Vent

centerline

A

B

C

D

E

F

H300

15”

10”

9”

28”

10”

15”

Additional Clearances For Backwall Exit

Unit

(with heat Shield)

Minimum Clearances:

To Combustibles

To Non-Combustibles

A

B

A

B

H300

9”

15”

0-9”

15

Min. Mantel Height (from fi nished fl oor):

48”

Max. Mantel Depth:

12”

Note: Floor protection must extend 2” to each side of the elbow.
Note: If side load door is used, fl oor protection must extend at least 18" (457mm) from
the side of the unit.

IF SIDE DOOR IS USED:

Floor protection must extend 18” (457mm) from the side of the

unit to the wall.

Floor protection must be a minimum of 3/8” thick with a

minimum k factor of 0.84.