background image

Catalog No.: 1000.96B

Effective: 11-15-07

Replaces: 10-15-01

Power Vent

For Raytherm 2100 - 4001

Model


Max. Runt (ft.)

Dimensions

Electrical Ratings

Raytherm

Model

MBTU

Vert. Horiz.

A

B

C

E

F

K

Volts Amps HP

Max. CFM

@ 70

°F

2100 2100 20 60 16-7/8 22-3/8 33-1/2 17-1/4 7-11/16 14 115 7.2 1/2

1900

2500 2499 20 60 16-7/8 22-3/8 33-1/2 21-3/4 12-3/16 14 115 7.2 1/2

1900

3001 3000 20 60 24-1/4 27-3/8 44-3/4 23-5/8 10-1/8 16 115 10.7 3/4

3400

3500 3500 20 60 24-1/4 27-3/8 44-3/4 29-1/4 15-3/4 16 115 10.7 3/4

3400

4001 4000 20 60 24-1/4 27-3/8 44-3/4 34-7/8 21-3/8 18 115 10.7 3/4

3400

Notes:

1. Vent pipe sizes are based on standard horizontal discharge with maximum sixty feet of horizontal length with

no elbows, 300°F nominal flue temperature, and sea-level operation. (Allow 10 ft. equivalent length
adjustment for each 90° elbow.) For installation under other conditions, please consult the factory.

2. Left discharge is standard.

3. Vent pipe must meet Category III appliance venting requirements.

4. Follow installation instructions provided by power vent manufacturer.


Raypak, Inc.

ƒ 2151 Eastman Avenue, Oxnard, CA 93030 ƒ (805) 278-5300 ƒ Fax (800) 872-9725 ƒ www.raypak.com