Catalog No.: 1000.70A

Effective: 10-15-07

Replaces: 5-1-05

D-2 Power Vent

For Heater Models 206-407

Heater Model



18-1/8

7-7/8

B

4" DIA

D

11-5/8


Dimensions (in.)

Heater

Model

Power Vent

Part No.*

B D

206/207 009832 12-3/8 4-1/4

266/267 009832 12-3/8 4-1/4

336/337 009833 18-1/8 7-1/4

406/407 009833 18-1/8 7-1/4

* Part numbers are for 240 VAC units.

Consult factory for 120 VAC units.


NOTES:
1. All units can exhaust flue gases horizontally or

vertically at up to 100 ft. of equivalent length
vent pipe
- 90° elbow = 10 ft. equivalent length
- 45° elbow = 5 ft. equivalent length

2. Vent pipe must meet Category III appliance

venting requirements.

3. Vent pipe sizes are based on 400°F nominal

flue temperature and sea-level operation. For
installation under other conditions, please
consult the factory.