Omron CS1W-ETN21 User Manual

Page 235

Advertising
background image

210

Troubleshooting Procedures

Section 8-4

8-4-2

FINS Communications Problems (SEND(090)/RECV(098)/
CMND(490))

Go to Network
Connection Problems

N

Y

Y

N

N

Y

N

Y

Set both nodes to the same FINS network address.

N

N

N

Y

Y

Y

N

Y

Y

FINS Communications Problems

occurred.

Is the control data

for the instruction set

incorrectly?

Make sure that the FINS network address is not set to 0
for the Ethernet Unit and check the network address,
node number and unit address.

Is a CMND(194)

instruction being addressed

to the local node, e.g. for

socket services?

Are different UDP port

numbers set for FINS

communications for both

the local node and the

remote node?

Are the local and remote
nodes both on the same

network, i.e. do they have the
same network number in their

IP addresses?

Set the same port number for both nodes.

Is the IP address

of the remote node missing from

the IP address table?

IP routing must be used if the net ID of the IP address of the
local node and remote node. Set the IP address of the remote
node in the local IP address table. (Note: Use of the IP address
table must be set in the mode settings for the IP address table to
be effective.)

Set the IP address of the remote
node in the IP address table or use
automatic address conversion.

Is the IP address

of the remote node

missing from the IP

router table?

Set the network number of the remote node in the IP
router table.

Are the FINS network

addresses of the local and

remote nodes different?

Are you attempting

a broadcast transmission?

Do not attempt to broadcast to a node with a different
network number. You can broadcast only to nodes on the
same IP network.

Are you attempting to

communicate with a PLC on

another network?

Are the routing

tables set improperly?

Y

Set routing tables at the local node, target node, and any
relay nodes.

(Note: The automatic generation setting cannot be used alone.)

E

N

D

Refer to 8-5 Troubleshooting
with Response Codes
and
remove any causes of the
problem discovered there
before proceeding with this
procedure.

Advertising