OPTI-UPS High-Frequency Online UPS DS6000E User Manual

Specifications features

Advertising
background image

Specifications

Features

*

Online Working Mode: All changeable structures, high output stability rate, zero out-off time.

*

Intelligent RS232 Communications Functions: To supervise and control the conditions of power supply and UPS

through OPTI-UPS powersoft power supply supervision and control software. Also supporting OPTI-UPS SNMP network

adapting apparatus to enhance the reliability of the system.

*

High Input Power Factor: The advanced PFC control technology to ensure input power factor larger than 0.95 when the

output is full-loaded, so as to reduce the load on the power network.

*

Minimized Size: To enhance reliability of operation and reduce costs for the user.

*

High Efficiency and Low Wearing: Efficiency higher by 10%, less energy consumption, lesser noise and longer usage life.

*

Full-range of Protection Functions: Provision of super-high output voltage protection, low battery protection, trio

super-high current protection and super-high input voltage protection, to enhance the adaptability to utility power supply

and impact proof and ensure the safe operation of the user’s equipment and the UPS.

*

Three-Classes Over-Current Protection

*

Input Over-Voltage Protection

* DS1000E / DS1000EL /

DS2000E / DS2000EL /

DS3000E / DS3000EL /

DS6000E / DS6000EL

DS1000E / DS2000E / DS3000E / DS6000E

DS1000EL / DS2000EL / DS3000EL / DS6000EL

High-Frequency Online UPS

Line Interactive

UPS Series

On Line UPS

Series

A

VR Series

Inverter Series

Surge Series

Standby UPS

Series

Networking

Series

Green Power

Series

MODEL NAME

DS1000E

DS2000E

DS3000E

DS6000E

DS1000EL

DS2000EL

DS3000EL

DS6000EL

INPUT

AC voltage range
Input Frequency range
Number of phases
Battery voltage (Vdc)

160 ~ 275 Vac

OUTPUT

Power
Voltage
Frequency
Wave form
Switching Time

OTHER FEATURES
Charge recovery time

Panel display

Warning functions

50 +/-5 % Hz

36

1000VA

Sockets

Sockets and Terminal

Terminal

72

2000VA

96

3000VA

120

6000VA

Three lines in single phase

230 +/-2% V

50 +/-0.2% Hz (battery mode)

50 +/-0.1% Hz (battery mode)

105%~125% Load, lasting 60
seconds. 125%~150% Load,

lasting 30 seconds.≥150% lasting

300 milliseconds

Sine wave THD < 3% (Linear load)

105%~130% Load, lasting 60 seconds.

135%~150% Load, lasting 30 seconds.

≥150% lasting 300 milliseconds

LED displays operation status of UPS

< 45

< 55

LED displays operation status and

LCD displays parameter of UPS

0~95% No condensation

490 x 198 x 347

465 x 155 x 225

637 x 253 x 680 637 x 253 x 500

0 ms

RS232 interface supports UPS power management software and SNMP protocol

<12 hours (Standard time delay model)

0 - 40 C

Battery low voltage protection, overload protection, short-circuit protection and excess temperature protection

Battery low voltage, abnormal power supply, UPS malfunction

36

94.5

18

38

17

32

8.5

15

Output mode

Communications interface

Protection function
Noise (dB)
Working temperature
Relative humidity
Dimensions (L x W x H) (mm)
Weight (kg)

Overload capacity

41-1.

Advertising