Powersense wiring & controls, Powersense, T5 dimming unv - dimming control wiring examples – Sylvania QUICKTRONIC POWERSENSE T5 User Manual

Page 3: 10v dc control with powersense ballasts, Wire powerline control with powersense ballasts

Advertising
background image

POWERSENSE

WIRING

&

CONTROLS

To
Fluorescent
Lamps

Violet (+)

DIMMING
BALLAST

Black
White

2-wire Powerline

AND

0-10Vdc Control with POWERSENSE Ballasts

0-10V

Control

Gray (-)

Neutral (White)

120 or 277V

Black (Hot)

LINE

Gray

Violet

Class 1 or Class 2 circuit

To
Fluorescent
Lamps

Violet (+)

DIMMING
BALLAST

Black
White

Gray (-)

To
Additional
Ballasts

2-wire

Fluorescent

Powerline Dimmer

Black

0-10Vdc Low Voltage
Industry Standard Interface
• Daylight Harvesting
• Building Management
• Demand Response Override

Fluorescent AC Dimming
No Control Wires
• Occupant Wallbox Dimming
• Lighting Panel Dimming
• Excellent for Retrofit

Industry’s 1st Ballast That Allows POWERLINE Fluorescent Control

AND

0-10Vdc Control Input Simultaneously

Line

Voltage

Switch

To
Fluorescent
Lamps

Violet (+)

DIMMING
BALLAST

Black
White

0-10V DC Control with POWERSENSE Ballasts

0-10V

Control

Gray (-)

Neutral (White)

120 or 277V

Black (Hot)

Black

Black

LINE

Gray

Violet

Class 1 or Class 2 circuit

To
Fluorescent
Lamps

Violet (+)

DIMMING
BALLAST

Black
White

Gray (-)

To
Additional
Ballasts

On/Off

Switch (120/277V)

Slide Dimmer

0-10V

0-10Vdc

Wallbox

Control with
Line Voltage

Switch

To
Fluorescent
Lamps

Violet (+)

DIMMING
BALLAST

Black
White

2-wire Powerline Control with POWERSENSE Ballasts

Gray (-)

Neutral (White)

Black (Hot)

LINE

CAUTION:

For 2-wire Powerline wiring, individually insulate (cap-off)

all unused Violet & Gray leads as shown.

To
Fluorescent
Lamps

Violet (+)

DIMMING
BALLAST

Black
White

Gray (-)

To
Additional
Ballasts

2-wire

Fluorescent

Powerline Dimmer

Black

To
Fluorescent
Lamps

Violet (+)

DIMMING
BALLAST

Black
White

2-wire Powerline Control with POWERSENSE Ballasts

Gray (-)

Neutral (White)

Black (Hot)

LINE

CAUTION:

For 2-wire Powerline wiring, individually insulate (cap-off)

all unused Violet & Gray leads as shown.

To
Fluorescent
Lamps

Violet (+)

DIMMING
BALLAST

Black
White

Gray (-)

To
Additional
Ballasts

2-wire

Fluorescent

Powerline Dimmer

Black

Powerline Control Specs:

Specification-grade controls are available for 120V or 277V

operation of controllable analog electronic fluorescent ballasts.

Controls must be suitably rated for both the type (e.g. Fluorescent

Phase-control) and size (e.g. 600W of the connected load.

Wallbox Style 2-wire Powerline Control Wiring Example

QUICKTRONIC

®

POWERSENSE

®

T5 Dimming UNV - Dimming Control Wiring Examples

Specifications subject to change without notice.

OSRAM SYLVANIA National Customer Service and Sales Center 1-800-LIGHTBULB (1-800-544-4828) www.sylvania.com

Item

OSRAM SYLVANIA

Input

Dimming

Maximum

Number Description

Voltage

Control

Power Rating

Wiring

Color

45167

ELMC-SL3W-TVWBX/UNV

120/277

0-10V

1200VA @120V

Single Pole White

1500VA @277V

or 3-way

ELOGIC

WALLBOX STYLE 0-10V DIMMER WITH POWER SWITCH

Item

OSRAM SYLVANIA

Voltage

Number

Description

Rating

Rating

Type

Wiring

45165

ELMC-SL3WHP-FLPCWBX120

120 VAC

1000VA

Fluorescent

Single Pole

45166

ELMC-SL3WHP-FLPCWBX277

277 VAC

1200VA

Phase cut

or 3-way

45163

ELMC-SL3WSP-FLPCWBX120

120 VAC

600VA

45164

ELMC-SL3WSP-FLPCWBX277

277 VAC

600VA

*For additional information refer to ELOGIC

Lighting Controls product information bulletins LMS068.

ELOGIC

MANUAL CONTROL SLIDE FLUORESCENT PHASE CUT DIMMER

Daylight Harvesting and Occupancy Control Wiring Example

To
Fluorescent
Lamps

Violet (+)

DIMMING
BALLAST

Black
White

Photo Sensor 0-10V Wiring Example

0-10V DC Control with POWERSENSE Ballasts

0-10V

Control

Gray (-)

Neutral (White)

120 or 277V

Black (Hot)

LINE

Gray

Viole

t

Class 1 or Class 2 circuit

To
Fluorescent
Lamps

Violet (+)

DIMMING
BALLAST

Black
White

Gray (-)

To
Additional
Ballasts

Photo

Sensor

0-10V

Standard

Line Voltage

Switch

Black

Single-Pole Wiring

Red

Red

3-Way Wiring

0-10V

Control

NOTE : Gray and violet wires are for SYLVANIA QUICKTRONIC
POWERSENSE dimming ballasts only. If 0-10V control is not
used, the gray and violet wires must be capped off separately.

Green (Ground)

Green (Ground)

Red

Blk

108

106

Optional Dimmer

120 or 277V Black (Hot)

White (Neutral)

Black

Black

Black

Black

Black

To
Fluorescent
Lamps

To
Fluorescent
Lamps

Violet (+)

Violet (+)

Violet

Gray (–)

Gray (–)

Gray

White

White

White

0-10V Dimming Output

for Daylight Harvesting

Dimming

POWERSENSE

Ballast

Dimming

POWERSENSE

Ballast

Black
(Hot)

White (Neutral)

White

Black

Violet (+)

Gray (-)

Black

(Occupancy Sw. Hot)

White

To
Additional
Ballasts

To
Additional
Ballasts

Black

Violet (+)

Gray (-)

*

*

For two-wire manual AC phase cut dimming controls see SYLVANIA ELOGIC

Lighting Controls product information bulletin LMS068.

Dimming

Ballast

AC Phase Cut & 0-10V

Dimming

Ballast

AC Phase Cut & 0-10V

0-10V Dimming Output
for Daylight Harvesting

Sensor

POWERSENSE

Dimming

Ballast

White (Neutral)

White
Black

Violet (+)

Gray (–)

White
Black

Violet (+)

Gray (–)

For two-wire manual AC phase cut dimming controls see SYLVANIA ELOGIC

Lighting Controls product information bulletin LMS068.

Black (Hot)

POWERSENSE

Dimming

Ballast

To Additional
Ballasts
(Maximum of 10 total).

Optional Dimmer

*

*

Wallbox Style 0-10V Control with Power Switch Wiring Example

Occupancy

Item

OSRAM SYLVANIA

Sensing

Control

Sensor

Mounting

Number Description

Function

Method

Method

Power

Method


45030 ELSC-DLH-TVLAMP/BUS

Daylight Harvesting

N/A

0-10V

From Ballast

To Lamp

45032 ELSC-DLOCIRM-TV1RCEIL/UNV

45033 ELSC-DLOCIR-TV1RCEIL/UNV

45034 ELSC-DLOCIRM-TV1RREC/UNV

45035 ELSC-DLOCIR-TV1RREC/UNV

*For additional information refer to ELOGIC

Lighting Controls product information bulletins ECS101 and ECS106.

ELOGIC

DAYLIGHT HARVESTING AND OCCUPANCY CONTROLS ORDERING INFORMATION

Daylight

Harvesting

+

Occupancy

Sensing

0-10V

+

Power

ON/OFF

switch

Passive

Infrared +

Microphonics

Passive

Infrared +

Microphonics

Passive Infrared

Passive Infrared

Line voltage

120/277AC

No power

pack required

Ceiling

Recessed

Advertising