Omega Speaker Systems DP18-AT2 User Manual

Dp18 series, Model dp18-at2 ac ammeter, Ac ammeter for current transformer x/5

Advertising
background image

An O ME GA Te c h n o l o g i e s Co m p a n y

M2099/1294

INSTRUCTION

SHEET

DP18 Series

Model DP18-AT2
AC Ammeter

CCD1294APC2BA

FIG. 3

A

C

E

G

F

D

B

PT1

GROSS SPAN ADJUSTMENT

SIGNAL INPUT

A

B

C

SPECIFICATIONS

DISPLAYS . . . . . . . . . . . . . . . . . . . . . . 3 digits, 7 segment, red LED
HEIGHT . . . . . . . . . . . . . . . . . . . . . . . . 0.56" (14.2 mm.)
SYMBOLS . . . . . . . . . . . . . . . . . . . . . . 1.8.8.8
DECIMAL POINTS . . . . . . . . . . . . . . . . Selectable by jumpers
OVERRANGE INDICATION . . . . . . . . . Display flashes

INPUT CONFIGURATION . . . . . . . . . . . Bipolar single
ZERO . . . . . . . . . . . . . . . . . . . . . . . . . Automatic
SPAN ADJUSTMENT . . . . . . . . . . . . . . ± 5 %

CONVERTER . . . . . . . . . . . . . . . . . . . . Dual-slope, average value
SIGNAL INTEGRATION PERIOD . . . . . 80 ms.
READ RATE . . . . . . . . . . . . . . . . . . . . 3.12 / sec.
RANGES . . . . . . . . . . . . . . . . . . . . . . . See table selection fig. 3
HOLD . . . . . . . . . . . . . . . . . . . . . . . . . Optional

NOISE REJECTION NMR . . . . . . . . . . . 50 dB. 50/60 Hz.
ACCURACY . . . . . . . . . . . . . . . . . . . . 0.2 % ± 1 count
WARMUP TO RATED ACCURACY . . . 5 minutes
SPAN TEMPCO . . . . . . . . . . . . . . . . . . 150 ppm.
ZERO TEMPCO . . . . . . . . . . . . . . . . . . 2.5 µV/°C.

OPERATING TEMPERATURE . . . . . . . 0 to 50 °C (32 to 122 °F)
STORAGE TEMPERATURE . . . . . . . . . -40 to 80 °C (-40 to 176 °F)
WEIGHT . . . . . . . . . . . . . . . . . . . . . . . . 310 gr. (0.68 lb)
CASE MATERIAL . . . . . . . . . . . . . . . . ABS, DIN 43700, black color
STANDARD POWER . . . . . . . . . . . . . . 115 Vac. ± 10 %, 50/60 Hz.
POWER CONSUMPTION . . . . . . . . . . . 5.5 VA for AC.
ELECTRICAL CONNECTIONS . . . . . . . Push-in cable connectors
BURN-IN . . . . . . . . . . . . . . . . . . . . . . . 24 h.

SPAN

OFFSET

1

10

D
C
B
A

+

-

REAR VIEW

Setpoint R1
(option)

Setpoint R2
(option)

FRONT VIEW

FIG. 2

FIG. 1

SIGNAL
INPUT

THE INPUT ALLOWS DIRECT CONNECTION TO A CURRENT TRANSFORMER (CT) WITH A 5 A. SECONDARY, WITHOUT NEED FOR AN
INTERMEDIATE STEPDOWN.

SPAN : ADJUST THE MAXIMUM READING.
OFFSET : NOT IN SERVICE

SPAN ADJUSTMENT IS ACCESSIBLE BEHIND THE LOW DOOR.

Isolated digital output

(option)

SIGNAL CONDITIONER
COMPONENTS VIEW

RANGE SELECTION

0.01

0.1

SELECTOR S1

HOLD,

latch the reading

display, while these pins
are linked

ANALOG OUTPUT
(OPTION)

POWER SUPPLY

see instrument label

0.1

1

150

150.0

G

250

250

B

400

400

C

500

500

D

600

600

E

1000

1000

F

1500

1500

G

AC AMMETER for current transformer X/5

CLOSE

RESOLUTION

READING

I NOMINAL

Amp.AC

Amp.AC

JUMPER

Amp.AC

Amp.AC

Amp.AC

5

5.00

D

10

10.00

F

15

15.0

A

25

25.0

B

40

40.0

C

50

50.0

D

60

60.0

E

100

100.0

F

JUMPER

Amp.AC

I NOMINAL

READING

CLOSE

RESOLUTION

PLACE THE PLUG-IN JUMPER ON THE
SELECTOR S1, IN FUNCTION OF THE
NOMINAL CURRENT TRANSFORMER,
AND THE DECIMAL POINT JUMPER
ON THE CORRESPONDING POSITION
(FIG.5). TO OBTAIN THE INDICATED
PERFORMANCE, USE CURRENT
TRANSFORMERS CLASS 0.5 OR BETTER.

½