Afety, Onsiderations – Omega Engineering DIN-RAIL DRN-PS-750 User Manual

Page 16

Advertising
background image

S

AFETY

C

ONSIDERATIONS

14

DNR-PS Ñ DIN Rail Power Supplies

Unpacking & Inspection

Unpack the instrument and inspect for obvious shipping damage. Do not attempt to operate
the unit if damage is found.

This instrument is a panel mount device protected in accordance with Class I of EN 61010
(115/230 AC power connections). Installation of this instrument should be done by Qualified
personnel. In order to ensure safe operation, the following instructions should be followed.

This instrument has no power-on switch. An external switch or circuit-breaker shall be included in the
building installation as a disconnecting device. It shall be marked to indicate this function, and it shall be
in close proximity to the equipment within easy reach of the operator. The switch or circuit-breaker shall
not interrupt the Protective Conductor (Earth wire), and it shall meet the relevant requirements of
IEC 947Ð1 and IEC 947-3 (International Electrotechnical Commission). The switch shall not be
incorporated in the mains supply cord.

Furthermore, to provide protection against excessive energy being drawn from the mains supply in case
of a fault in the equipment, an overcurrent protection device shall be installed.

¥

The Protective Conductor must be connected for safety reasons. Check that the power
cable has the proper Earth wire, and it is properly connected. It is not safe to operate this
unit without the Protective Conductor Terminal connected.

¥

Do not exceed voltage rating on the label located on the top of the instrument housing.

¥

Always disconnect power before changing signal and power connections.

¥

Do not use this instrument on a work bench without its case for safety reasons.

¥

Do not operate this instrument in flammable or explosive atmospheres.

¥

Do not expose this instrument to rain or moisture.

EMC Considerations
¥

Whenever EMC is an issue, always use shielded cables.

¥

Never run signal and power wires in the same conduit.

¥

Use signal wire connections with twisted-pair cables.

¥

Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems persist.

This device is marked with the international Caution symbol. It is important to read this
manual before installing or commissioning this device as it contains important information
relating to Safety and EMC (Electromagnetic Compatibility).

Note

Note