Maintenance bypass switching, Planning, Warning: shock hazard or equipment damage – Outback Power Systems GS8048 User Manual

Page 18

Advertising
background image

Planning

16

900-0021-01-00 Rev A

Maintenance Bypass Switching

Inverter systems are often equipped with AC maintenance bypass switches or interlocks. If the
inverter system ever needs to be shut down or removed, the AC sources and loads must be
disconnected. A bypass device allows the AC source to deliver power directly to the loads, bypassing
the inverter. This can minimize disruption to the system and avoids the need for extensive rewiring.

Figure 4

Bypass Switching

The GSLC (see page 12) can be equipped with bypass circuit breakers for this purpose. However, if
multiple Radian inverters are stacked in a single system, then the bypass function must be
simultaneous for all inverters. The GSLC bypass kits operate independently, not simultaneously, and
should not be installed in this kind of application. Both manual and automatic double-pole,
double-throw bypass switches are commonly available in a range of sizes and options. These are
highly recommended for systems with more than a single inverter.

WARNING: Shock Hazard or Equipment Damage

Using independent bypass devices on multiple inverters can result in power being routed
to inappropriate places. This could create an electric shock hazard or damage the
equipment.

Figure 5

Bypass Switching for Multiple Inverters

AC Source

AC Loads

GSLC Bypass

Inoperative

Radian

Inverter

Input Wiring

Output Wiring

AC Source

AC Loads

Output Wiring

Inactive Radian Inverters

Input Wiring

GSLC Bypass Devices

(not to be used)

External Bypass Device

Advertising