4.4 Open Thermocouple Detection

The OME-DB-889D provides open thermocouple detection through a resistor

circuitry. These resisters are normally not connected. The user can find on the back of
the board has two solder gaps for each input channel. If you short the solder gaps, the
open thermocouple detection is enabled.

Channel 0 High

1.2K

-15V

1uF 50V

OME-DB-889

1.2K

37Pin Cable

GND

Channel 0 Low

HJ0

100M

10K

LJ0

Note:
If a thermocouple opens, the bias resistor will slowly pull the input voltage to
-10V then user can use a simple application program to detect the voltage
change.