5. - Entering the High Alarm Level

Press the SELECT button again

- the High Level Alarm Point

indicator LED on the graphic face and the top RED line in the bar graph display will flash.

P___

P___

P___

P___

P___ appears

in the display. Enter the level, using the INCREASE or DECREASE arrow to set the desired level. When
this point or level is reached, it will indicate a High Level Alarm has been reached and activate the control
circuit/device you have designed into your system.

6. - Entering the Sump ON Level

Press the SELECT button again

- the yellow Sump ON indicator

LED will flash along with the YELLOW line in the bar graph.

P___

P___

P___

P___

P___ appears in the display. Enter the

level, using the INCREASE or DECREASE arrow to set the desired Sump ON level. When this point or
level is reached, LVCN-302 will deactivate the differential output relay to the control circuit/

7. - Entering the Sump OFF Level

Press the SELECT button again - the Sump OFF indicator LED

and the ORANGE line in the bar graph will flash.

P___

P___

P___

P___

P___ appears in the display. Enter the Sump OFF

level, using the INCREASE or DECREASE arrows. When this point or level is reached, LVCN-302 will
activate the differential output(s) to the control circuit/device you have designed into your system.

device you have designed into your system.

8. - Entering the Low Alarm Level

Press the SELECT button again - the Low Level Alarm Point

indicator LED on the graphic face and the top RED line in the bar graph display will flash.

P___

P___

P___

P___

P___ appears

in the display. Enter the Low Alarm Level, using the INCREASE or DECREASE arrow. When this point or
level is reached, it will indicate a Low Level Alarm has been reached and activate the control circuit/device
you have designed into your system.

12. High Level N.C.

11. High Level Com

10. High Level N.O.

9. Sump ON N.C.

8. Sump ON Com

7. Sump ON N.O.

6. Low Level N.C.

5. Low Level Com

4. Low Level N.O.

3. Sump ON N.C.

2. Sump ON Com

1. Sump ON N.O.

Signal Power Supplied by LVCN-302 (Loop Powered)

123456

123456

123456

123456

+24 VDC Output

Level Input
Transducer

Signal Power Supplied by Other Source

Sensor Input Connections / Schematics

Typical Form-C Relay Connection

Sending 4-20ma Signal to Other Devices

4. 4-20 mA ( - )

3. 4-20 mA ( + )

2. Ground

1. + 24 VDC Out

Sensor Input

Terminal

+

Level Input
Transducer

Sensor Input

Terminal

External

Power

Supply

+

Sensor Input

Terminal

LVCN-302
Sensor Input

3.

4.

+

Sensor Device

PLC

+

+

1.

(Transmitter)

4-20mA ( +)

3.

2.

4.

Jumper #4 to #2

4. 4-20 mA ( - )

3. 4-20 mA ( + )

2. Ground

1. + 24 VDC Out

4.

3.

123456

123456

123456

123456

-

-

+

(Transmitter)

+

4. 4-20 mA ( - )

3. 4-20 mA ( + )

2. Ground

1. + 24 VDC Out

-

-

-

-

Form - C

10.0 Amp @ 120 VAC

(noninductive)

Relay operates at
same level as #7-#9.
Consider it a spare
Form C sump relay.

9.

8.

7.

3.

2.

1.