MAKING AND BREAKING CAPACITY

SWITCH SELECTION AND MOUNTING INSTRUCTIONS

• Select a switch such that the desired switching point falls roughly

in the middle of the adjustment range.

• Do not exceed switch electrical ratings. Use an appropriately sized relay when

switching larger electrical loads.

• For liquid media with pressure spikes and/or pulsating pressures, install a

pressure snubber.

• For outdoor applications, sufficient protection must be provided.

ADJUSTMENT OF SWITCHING POINT

Either the upper or the lower switching point may be adjusted.
The opposite one is then fixed by the hysteresis characteristics of the switch.
Use a pressure gauge for exact adjustment. Proceed as follows:
1. Loosen locking screw.

2. Adjust the switching point using a 5-mm hexagon wrench.

Clockwise rotation increases switching pressure and
counter-clockwise rotation decreases switching pressure.
Low-end of adjustment range is reached when top of
adjustment barrel is approximately level with top of switch
housing. High-end of adjustment range is reached when
adjustment barrel is fully CW.

3. Re-tighten locking screw.

TYPE

TYPE

VMIN

MAXIMUM PERMANENT

CONTACT LIFE

LOAD

OF

OF

[V]

CURRENT IMAX [A] AT V

ELECTRICAL

MECHANICAL

LEVEL*

CURRENT

LOAD

24 V

125 V

250 V

AT IMAX

AT I

0

Standard

AC

Resistive

12

5

5

5

5 x 10

4

approx 10

7

(relays,

switching

switching

solenoids)

AC

Inductive

12

3

3

3

cycles

cycles

PF

.7

DC

Resistive

12

5

.4

_

DC

Inductive

12

3

.05

_

L/R

10 ms

Low

AC

Resistive

5

.34

.08

.04

2 x 10

5

approx 10

7

(electronic

switching

switching

circuits)

DC

Inductive

5

.1

_

_

cycles

cycles

L/R

10 ms

*Load Level Explanation
PSW18H Series pressure switches have microswitch
contacts with gold plating over silver base metal. The gold
plating remains intact when “low level” voltage / current
levels are observed. This feature assures highly reliable
switching in low-level electronic circuits.

Standard applications do not require the gold plating – which
will decay naturally when switching larger electrical loads.

Notes:
1. Reference conditions:

30 cycles per min and 86°F (30°C) ambient.

2. Reducing load current to 50% of Imax approximately

doubles contact life.

Adjustment Of Switching Points