WIRE SIZES

The following chart contains information on wire sizes, the DC resistance of the wires and the corresponding diameters and areas of
these wires. This information can be used to calculate the voltage drop of the wires or to find an equivalent wire size.

CROSS-SECTIONAL AREA

APPROXIMATE

DIAMETER

SIZE

(AWG)

DC

Resistance

in Ohms

(1000 feet)

SQUARE

INCHES

SQUARE

MILLIMETERS

INCHES

MILLIMETERS

14

3.14

.0032

2.08

.078

1.98

12

1.98

.0051

3.31

.101

2.57

10

1.24

.0082

5.26

.126

3.20

8

0.78

.0130

8.37

.162

4.11

6

0.50

.0206

13.30

.215

5.46

4

0.31

.0328

21.15

.269

6.83

2

0.19

.0521

33.62

.337

8.56

1

0.15

.0657

42.41

.376

9.55

1/0

0.12

.0829

53.50

.423

10.74

2/0

0.10

.1045

67.43

.508

12.90

3/0

0.08

.1318

85.01

.576

14.63

4/0

0.06

.1662

107.20

.645

16.38