2 output when an error or alarm occurs – Toshiba Tohsiba Electromagnetic Flowmeter Converter L5232 User Manual

Page 157

Advertising
background image

6F8A0917

- 156 -

12.2

Output When an Error or Alarm Occurs

Error indication

Measured value
display

Current output
(4 to 20mA)

Totalizer pulse
output

Remarks

ROM ERROR

(Note

1)

4mA (standard)
(Note

3)

Stopped

After power-up, measurement
does not start.

RAM ERROR

4mA (standard)
(Note

3)

Stopped

After power-up, measurement
does not start.

PARAMETER FAIL
(Note

2)

Zero

4mA (standard)
(Note

3)

Stopped

EX.CURR OPEN

Zero

4mA (standard)
(Note

3)

Stopped

Still water zero adjustment
cannot be conducted.

EX.CURR ERROR

Zero

4mA (standard)
(Note

3)

Stopped

ADC ERROR

Zero

4mA (standard)
(Note

3)

Stopped

EMPTY

Zero

4mA (standard)
(Note

3)

Stopped

Still water zero adjustment
cannot be performed.

INVALID TOTAL

Measured value Measured value Measured value The error message disappears if

you clear (reset) the totalizer.

HIGH ALARM

Measured value Measured value Measured value

H-HIGH ALARM

Measured value Measured value Measured value

L ALARM

Measured value Measured value Measured value

L-LOW ALARM

Measured value Measured value Measured value

Note 1: The display and output may be uncertain depending on the nature of the ROM error.
Note 2: If a parameter failure relating to the current output occurs, the current output may not become exactly

the set value of the current output used when an alarm occurs.

Note 3: The output becomes the value selected in 8.2.11 “Current Output Setting Used When an Alarm

Occurs.”

Note 4: If the fluid empty alarm not included (WITHOUT EMP) is selected (standard) in the setting for alarm

output factors in 8.2.19 “Self-Diagnosis Function,” the output becomes 4mA and if the fluid alarm
included (WITH EMP) is selected, the output becomes the same as the above in Note 3.

Advertising