Toshiba Tosvert Inverter E6580772 User Manual

Page 14

Advertising
background image

E6580772

13

Parameter name

Title

Setting value

Details

Com. Error
selection

f850

0

to 4

Sets the inverter operation at time of communication error.
The action of inverter will be different depending on the
status (during operation or halt) of the inverter. (Note 2)

0: During halt

Inverter stops after free run.

During operation

Inverter trips.

1: During halt

Inverter stops after free run.

During operation

Inverter stops after free run.

2: Invalid

(Setting is enabled with F10M
option connected.)

3: During halt

Inverter decelerates to stop.

During operation

Inverter decelerates to stop.

4: During halt

Inverter continues to run.

During operation

Inverter continues to run.

Com. Error
detecting time

f851

0

to 1000

Sets the time until the communication error is detected.
Setting is done by a unit of ms. (Note 3)

Reset function

f899

0

, 1

Resets the inverter station.

0: No action
1

: To reset the inverter station. After resetting, setting

data returns to 0.

(Note 1) For setting the parameters, never duplicate the station address on the same communication line.

PLC rink relay register is automatically allocated according to the setting of the station address. As for the

setting of station addresses, consider the allocation of rink relay register that is determined by the other

station addresses and the number of words that have been set in the parameters f831 to f836, and

f841

to f846.

The maximum setting value for station address is 255, however when 255 is set, only one word of scan

data can be set. To set the scan data in its maximum value of 12 words, setting value of the station

address should be: 255-(12-1)= 244.

(Note 2) Setting of “free-run stop” is valid when the “operation command mode selection” [cmod] is

selected to the optional add-on cassette.

Setting of “deceleration stop” is valid when the “operation command mode selection” [cmod] is selected

to the optional add-on cassette or when the “speed setting mode selection” [fmod] is selected to the

optional add-on cassette. At the same time the deceleration stop returns the command of run/stop and the

speed reference value to 0. Except when the above command setting is selected, inverter cannot be

stopped.

Furthermore when the “operation command mode selection” [cmod] is set to other than the optional

add-on cassette and when the “speed setting mode selection” [fmod] is selected to the optional add-on

cassette, in some cases inverter can not stop running because of the setting of the parameters (zero-

speed operation setting). Torque control is valid when the “operation command mode selection” [cmod]

is set to the optional add-on cassette, but the inverter operation becomes “free-run stop” at that time.