Electrical wiring filter installation – Trane WCY024G1 User Manual

Page 12

Advertising
background image

Page 12

ELECTRICAL CONNECTIONS

Electrical wiring and grounding must be installed in accordance with
local codes or, in the absence of local codes, with the National
Electrical Code ANSI/NFPA 70, Latest Revision.

ELECTRICAL POWER

It is important that proper electrical power be available for the unit.
Voltage variation should remain within the limits stamped on the unit
nameplate.

DISCONNECT SWITCH

Provide an approved weather-proof disconnect either on the side of
the unit or within close proximity and within sight of the unit.

OVER CURRENT PROTECTION

The branch circuit feeding the unit must be protected as shown on
the unit rating plate.

POWER WIRING

The power supply lines must be run in weathertight conduit to the
disconnect and into the bottom of the unit control box. Provide strain
relief for all conduit with suitable connectors.

Provide flexible conduit supports whenever vibration transmission
may cause a noise problem within the building structure.

Be sure all connections are made tight. See Figure 14.

NOTES: For branch circuit wiring (main power supply to unit
disconnect), wire size for the length of run should be determined
using the circuit ampacity found on the unit nameplate and the
N.E.C.
For more than 3 conductors in a raceway or cable, see the
N.E.C. for derating the ampacity of each conductor.

GROUNDING: THE UNIT MUST BE ELECTRICALLY GROUNDED
IN ACCORDANCE WITH LOCAL CODES OR THE NATIONAL
ELECTRIC CODE.

NOTE: Ground the unit internally as provided. See wiring
diagram for location.

ELECTRICAL WIRING

FILTER INSTALLATION

*Filters must be installed in the return air system. The above
square footages are based on 300 F.P.M. face velocity. If
permanent filters are used, size per mfg. recommendation
with clear resistance of 0.05"WC.

TABLE 1

AIR FILTERS

Filters are to be used with the WCY024-060G heating/cooling
units. The basic unit does not have filters in it. However, a filter
frame accessory is offered that will allow filters to be installed
within the unit.

Otherwise a filter rack must be installed by the installer in the
duct work.

Affix the filter label supplied with the unit adjacent to the filter
area.

THERMOSTAT HEAT ANTICIPATOR

The thermostat heat anticipators should be set to equal the amper-
age draw of the W1 thermostat circuit.

IMPORTANT: Upon completion of wiring check all electrical
connections, including factory wiring within the unit.
Make sure
all connections are tight. Replace and secure all electrical box
covers and access doors before leaving the unit or turning on the
power to the unit.

CONTROL WIRING (CLASS II)

Low voltage control wiring should not be run in conduit with power
wiring unless Class 1 wire of proper voltage rating is used. Route
the thermostat cable or equivalent single leads of No. 18 AWG
colored wire from the thermostat subbase terminals through the
rubber gromment on the unit. See Figure 5 for the control entry
location. Make connections as shown on the unit wiring diagram
and in Figure 14.

Do not short thermostat wires since this will damage the control
transformer.

Recommended wire sizes and lengths for installing the unit thermo-
stat are provided in Table 2. The total resistance of these low
voltage wires must not exceed one (1) ohm. Any resistance in
excess of 1 ohm may cause the control to malfunction because of
the excessive voltage drop

TABLE 2

THERMOSTAT WIRE SIZE AND MAXIMUM LENGTH

WIRE SIZE

MAXIMUM LENTGH (Ft)

18

75

16

125

14

200

UNIT

NOMINAL

CFM

FILTER*

(Sq Ft) SIZE

FILTER

RESISTANCE

WCY024G

800

2.67

0.05

WCY030G

1000

3.33

0.05

WCY036G

1200

4.00

0.05

WCY042G

1400

4.67

0.05

WCY048G

1600

5.33

0.05

WCY060G

2000

6.67

0.05

Advertising
This manual is related to the following products: