such as air conditioning compressors or to an electric
utility company problem. Arrange for correction of the
voltage as appropriate.

4E-2. Control Circuit Trouble Shooting

The heater controls are in a 24V 60 Hz circuit

with operating and safety controls basically arranged
in a series circuit. Trouble shooting is done by probing
for voltage at various points in the circuit to determine
which component is preventing operation. Check points
are indicated on Figure 31. The recommended
procedure steps through the circuit in a sequential way,
but verifying voltage at any of the numbered points
confirms that all prior components are OK.
Experienced technicians may be able to shorten the
process by going directly to one of the intermediate test
points.

4E-2a. Transformer

Attach one lead of the voltmeter to the

transformer terminal with a yellow wire attached to it,
which is point 11 on Figure 31. (This lead can be left
in place for most of the testing.) Touch the free lead of
the meter to the transformer terminal with a red wire,
point 1. The meter should show 20-28 volts. If there is
no voltage, replace the transformer.

4E-2b. Fuse

Leaving the “common” voltmeter lead in place at

point 11, touch the free probe to point 2. This is the
terminal block screw attached to the red wire from the
in-line fuse, and absence of voltage indicates a
defective fuse. If there is no voltage, inspect the rest of
the wiring to be sure that there is no “short” such as
contact of a terminal with the heater chassis or another
terminal. Correct any such condition and replace the
fuse.

Electronic

Temp

Control

Remote Connector

Water

Temp

Sensor

Pressure

Switch (Water)

OFF

Limit

Limit

Electrical

Fuse

Fireman

Switch

Connection

115V 60Hz

Blower

Igniter

Venturi Pressure

Switch

Vent Limit

Burner Limit

(Single Use)

Gas Valve

Ignition
Control

Fenwal
05-33

S120

L1

L2

S2

TH

MVI

G

F1

F2

24V

IND

Y

Y/BK

BR

W

W

W

BK

W-BK

Y
Y

Y/BK

Y

Figure 31. Wiring Diagram with Test Points.

Y

(MR)

PR

BR

Y/BK

W

W

BK

N

BK

BK

W-R

R

G

L1

R

W

BK

5

4

3

2

1

11

A

B

D

C

E

6

7

10

9

24V

IGN

GND

G

8

VAL

IGN/120

8

SPA

POOL

PSW

PV

MV

Advertising