8

APPLICABLE CONTROLS

REQUIREMENT

• When you use this air conditioner for the first time,

it takes approx. 5 minutes until the remote control
becomes available after power-on. This is normal.
<When power is turned on for the first time after
installation>

It takes approx. 5 minutes until the remote control
becomes available.

<When power is turned on for the second (or
later) time>

It takes approx. 1 minute until the remote control
becomes available.

• Normal settings were made as factory default.

Change the indoor unit settings as required.

• Use the wired remote control to change the

settings.

„

Changing applicable control
setting

Basic procedure for changing settings
Change the settings while the air conditioner is not
working.
(Be sure to stop the air conditioner before making
settings.)

Procedure

1

Push

button and temp. setup

button

simultaneously for at least 4 seconds.
After a while, the display flashes as shown in the figure.
Confirm that the CODE No. is [01].
• If the CODE No. is not [01], push

button to erase

the display content, and repeat the procedure from
the beginning.
(No operation of the remote control is accepted for a
while after

button is pushed.)

Procedure

2

Each time you push

button, indoor unit

numbers in the control group change cyclically. Select
the indoor unit you want to change settings for.
The fan of the selected unit runs and the louvers start
swinging. You can confirm the indoor unit for which you
want to change settings.

* The settings cannot be changed using the

wireless remote control, sub remote control,

or remote-controlless system (for central

remote control only). Therefore, install the

wired remote control to change the settings.

Power

on

“SETTING”

flashes

“SETTING”

goes out

Remote

control is

available

Approx. 5 minutes

Power

on

“SETTING”

flashes

“SETTING”

goes out

Remote

control is

available

Approx. 1 minutes

1

6

1

3

2

5

4

(* Display content varies with

the indoor unit model.)

22-EN