SPECIFICATIONS

PROTOCOLS

Power

24 VDC +/-10%, 2 W maximum

Toshiba T-Series PLCs

Keypad IP65

rated

keypad

Toshiba V-Series Integrated Controllers

Temperature

Operating: 0 to 50 degrees C
Storage: -25 to 80 degrees C

Toshiba G7/S9/VF_nC1 ASDs
Modbus

Humidity

10% to 90% (Non condensing)

Special (check with Toshiba)

Bezel Size

101.30 H X 182.50 W, Depth:36.80
mm

Panel cutout

79.00H X 162.00 W mm

Communication

Connects to PLC RS232/R485 port

Immunity to ESD

Level 3 as per IEC1000-4-2

Immunity to Transients Level 3 as per IEC1000-4-4

Radiated Susceptibility Level 3 as per IEC1000-4-3

Emission

EN55011 CISPR A



ORDER NUMBERS

DIMENSIONS

Part Numbers Description
OIS40R

Operator Interface Station.

TKRS485

RS485 Communication Cable T2N) 2m w/ 15
pin D shell & pigtail.

CAB-OIS-T1-X

RS232 Communication Cable 2m w/ 8 pin
mini DIN & 9 pin D-shell (T1)

CAB-OIS-T2-X

RS232 Communication Cable (T2E/T2N/T3)

9830

Beldon RS485 Cable (or equivalent)
Communications Cable 24 AWG low
capacitance (T1, T2E, V-Series)

26-117B

RadioShack RS232 Programming Cable
(or equivalent), 9 pin D shell (male & female)

Note: The OIS40R has a 9 pin D shell female connector for connection to the PLC. This connector can be setup as either
RS485 or RS232. For RS485 connection, one end of the Beldon 9830 cable must be terminated with a 9 pin D shell (male)
connector.