Page 26

MAINTENANCE

RECOMMENDED INSPECTION AND
MAINTENANCE TYPES

NOTE:

Refer to the SAFETY section of this
manual for important information.

A. Acceptance Inspection

This inspection confirms that the circuit
breaker unit is complete, correct as specified,
and undamaged from shipment. The
procedure for this inspection is outlined in the
RECEIVING, INSPECTION AND HANDLING
section of this manual.

B. Patrol Inspection

Inspection is made of the condition of the
circuit breaker while it is energized. Check
that no unusual sounds or smells exist
externally.

Inspection Frequency: Once every 6 months

C. Periodic Inspection

Inspection is performed wth the circuit
breaker de-energized. The lubrication of
sliding and rotating parts is checked and the
mechanism is lubricated if needed.

Inspection Frequency: Once every 1-3 years
or every 3000 operations (normal). Once
every 6 years (detailed).

Refer to Table 2 for the schedule of Periodic
Inspections.

D. Unscheduled Inspection

Inspections are implemented as required.

Inspection Frequency: As needed

NOTE:

The inspection frequency and points
to be inspected may vary from the
above recommendations depending
on the status of use, frequency of
switching, amount of current
interrupted and other factors.

Table 1 Tightening Torques

Screw

Nominal

Dia.

Tightening Torque

M4

15-20 kgf-cm
13-17 in-lb

M5

30-40 kgf-cm ()
26-34 in-lb

M6

50-65 kgf-cm ()
43-56 in-lb

M8

120-150 kgf-cm ()
9-11 ft-lb

M10

250-315 kgf-cm ()
18-23 ft-lb

M12

450-565 kgf-cm ()
32-41 ft-lb