TROUBLESHOOTING

You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition
to using the check codes displayed on the wired remote controller of the indoor unit.
Use the LEDs and error codes for various checks. Details of the error codes displayed on the wired remote
controller of the indoor unit are described in the Installation Manual of the indoor unit.

Verifying Error code status (Outdoor control
board)

1. Check that DIP switch SW803 is set to off.
2. Record the states (on or off) of LED 800 to LED 804

(Display mode 1).

3. Press SW800 for at least 1 second. The LED status

changes to display mode 2.

4. Since display mode 1 covers multiple errors with the

same code display, mode 2 must also be used to
determine the final error. Use the status recorded for
LED 800 to LED 804 in display mode 1 (Item 2
above) and combine it with the status for the same
LED’s in display mode 2 (Item 3 above) to determine
the complete error code using the chart below.

Verifying Error code status stored in
memory (Outdoor control board)

1. Check that DIP switch SW803 is set to on.
2. Record the states (on or off) of LED 800 to LED 804

(Display mode 1).

3. Press SW800 for at least 1 second. The LED status

changes to display mode 2.

4. Since display mode 1 covers multiple errors with the

same code display, mode 2 must also be used to
determine the final error. Use the status recorded for
LED 800 to LED 804 in display mode 1 (Item 2
above) and combine it with the status for the same
LED’s in display mode 2 (Item 3 above) to determine
the complete error code using the chart below.

NOTE

An outside air temperature (TO) sensor error can be
checked only when an error occurs.

No.

Cause

Display mode 1

Display mode 2

D800

D801

D802

D803

D804

D800

D801

D802

D803

D804

1

Normal

2

Discharge (TD) sensor error

{

{

{

3

Heat exchanger (TE) sensor error

{

{

{

4

Heat exchanger (TL) sensor error

{

{

{

5

Outside air temperature (TO) sensor error

{

{

{

6

Suction (TS) sensor error

{

{

{

7

Heat sink (TH) sensor error

{

{

{

8

Outdoor temperature sensor (TE/TS) connection

error

{

{

{

9

Outdoor EEPROM error

{

{

{

10

Compressor lock

{

{

11

Compressor lock

{

{

12

Current detection circuit error

{

{

13

Thermostat for compressor activated

{

{

14

Model data not set

(on the service P.C. board)

{

{

{

15

MCU-MCU communication error

{

{

{

16

Discharge temperature error

{

{

{

{

17

Abnormal power

(open phase detected or abnormal voltage)

{

{

{

{

18

Heat sink overheat

{

{

{

{

19

Gas leak detected

{

{

{

{

20

4-way valve reverse error

{

{

{

{

21

High pressure release operation

{

{

{

{

20-EN