SSP-PRC002-EN

Jobsite
Connections

Wiring shown with dashed lines is to be
furnished and installed by the customer.
All customer- supplied wiring must be
copper only and must conform to NEC
and local electrical codes. Codes may
require line of sight between disconnect
switch and unit.

NOTE:
1. When electric heater accessory is used
single point power entry or dual point
power entry is field optional. Single point
power entry option is through electric
heater only.

TWA050/TWE050
Field Wiring:
A

— 3 power wires. Line voltage.

B

— 3 power wires. Line voltage.

C

— Heat pump thermostat: 6 wires,

24 volts.

— Electric heat: add 2 additional

wires, 24 volts.

D

— 2 wires, 24 volts.
— Outdoor thermostat: add 1

additional wire per ODT, 24 volts.

— Electric heat: add 1 additional

wire, 24 volts.

(2) TWA050/TWE100B
Field Wiring:
A

— 3 power wires. Line voltage.

B

— 3 power wires. Line voltage.

C

— Heat pump thermostat: 7 wires,

24 volts Electric Heat: add 2
additional wires, 24 volts.

D

— 5 wires, 24 volts to outdoor

section ‘’A’’ 2 wires, 24 volts to
outdoor section ‘’B’’ 2 wires, 24
volts between outdoor sections
‘’A’’ ‘’B’’

— Electric heat: add 1 additional

wire, 24 volts.

— Outdoor thermostat: add 1

additional wire, 24 volt.

TWA075A/TWE075A;
TWA100A/TWE100A
Field Wiring:
A

— 3 power wires, line voltage.

B

— 3 power wires, line voltage.

C

— Heat pump thermostat: 6 wires,

24 volts.

— Electric heat: add 2 additional

wires, 24 volts.

D

— 6 wires, 24 volts.
— Outdoor thermostat: add 1

additional wire, 24 volts.

— Electric heat: add 1 additional

wire, 24 volts.

(2) TWA075A/TWE155B;
(2) TWA100A/TWE200B
Field Wiring:
A

— 3 power wires, line voltage.

B

— 3 power wires, line voltage.

C

— Heat pump thermostat: 7 wires,

24 volts.

— Electric heat: add 2 additional

wires, 24 volts.

D

— 9 wires, 24 volts.
— Electric heat: add 4 additional

wires, 24 volts.

— Outdoor thermostat: add 3

additional wires, 24 volts.

TWA155B/TWE155B;
TWA200B/TWE200B
Field Wiring:
A

— 3 power wires, line voltage.

B

— 3 power wires, line voltage.

C

— Heat pump thermostat: 7 wires,

24 volts.

— Electric heat: add 2 additional

wires, 24 volts.

D

— 7 wires, 24 volts.
— Electric heat: add 4 additional

wires, 24 volts.

— Outdoor thermostat: add 1

additional wire, 24 volts.