(8) ECONO. operation control

When the ECONO. button of the remote control-
ler is pushed, quiet and mild operation is per-
formed by restraining air flow and operating
motor speed.

1) Indoor air flow is controlled between SUL

and L– (Low air (–)).

2) Setting 10 at 16 rps and 13 at 20 rps as the

maximum operating compressor motor
speed, the minimum capacity operation range
is widened every 1 hour and 2 hours have
passed after ECONO. operation had started.

Fig. 8-2-4

–0,5

0

+0,5

+1,0

+1,5

+2,0

+2,5

*1

L–

SUL

(Room temp

.)

(Set temp

.)

Set
temp.

NOTE :

*1 : Middle motor speed between L– and SUL

Fig. 8-2-5 Setting of air flow

0,5

1

1,5

2

2,5

3

3,5

(Room temp

.)

(Set temp

.)

Air volume

Compressor motor speed

13 rps

13 rps

SUL

20 rps

16 rps

L–

17 rps

15 rps

{(L–) + (SUL)}/2

13

10

Time

2H

1H

8-2-2. DRY Operation

(The Remote Controller MODE Button
is Set to the DRY Position)

• Once the setting is made, the operation mode is

memorized in the microcomputer so that the
same operation can be effected thereafter simply
by pushing [START/STOP] button.

• Dry operation signal is transmitted to outdoor

unit.

• The Cooling operation giving priority to dehumidi-

fying, which restrains the indoor fan speed and
compressor motor speed, is performed.

• The indoor fan motor operates as shown in Fig.

8-2-5. (Fan speed is AUTO only.)

• The outdoor unit controls the outdoor fan relay

R01, R02 and R03, and the compressor motor
speed according to the operation command
signal sent from the indoor unit.