5. Modbus Module Operation

5.1. Modbus Commands


When a MODBUS command is used, the Modbus module translates it to the
corresponding T2 register access protocol.

MODBUS FUNCTION CODE

T2 COMMAND

01 Read Coil Status

DR Read Device/Register

02 Read Input Status

DR Read Device/Register

03 Read Holding Register

DR Read Device/Register

04 Read Input Register

DR Read Device/register

05 Force Single Coil

DW Write Device Register

06 Force Single Register

DW Write Device/Register

08 Loop Back Diagnostic test

**** Not Supported by EX10-MML11

15 Force Multiple Coils

DW Write Device/register

16 Preset Multiple Registers

DW Write Device/register



For more information on the Modbus protocol, please refer to the Modbus Protocol Reference
Guide, see

Additional References

.



For more information on the T2 register access protocol, please refer to the Computer Link
Function Operation Manual, see

Additional References

.